Terminal assignment
Terminal strip X6
View
Cable cross−sections and screw−tightening torques
Cable type
Flexible
We recommend to use control cables with a cable cross−section of 0.25 mm
EDKCSEE040 DE/EN/FR 3.0
Terminal
Function
X6/+24
Low−voltage supply of control
electronics
X6/GND
Reference potential low−voltage
supply
X6/T1
Thermostat contact 1
X6/T2
Thermostat contact 2
X6/D24
Low−voltage supply X6/DO1
(digital output 1)
X6/DO1
Digital output 1
(for central controller enable
signal to connected axis
modules)
X6/DI1
Digital input 1
(for power supply enable/charge
of the DC bus)
X6/DI2
Digital input 2
(for central controller enable
signal to connected modules;
available at output X6/DO1)
Wire end ferrule
Cable cross−section
Without wire end
0.08 ... 1.5 mm
ferrule
(AWG 28 ... 16)
With insulated wire
0.25 ... 0.5 mm
end ferrule
(AWG 22 ... 20)
l
Electrical installation
Control terminals
Electrical data
20 ... 30 V DC, 0.5 A (max. 1 A)
for 24 V starting current:
max. 2 A for 50 ms
18 ... 30 V DC
24 V DC, 0.7 A (max. 1.4 A)
short−circuit−proof
LOW:
−3 ... +5 V;
−3 ... +1.5 mA
HIGH:
+15 ... +30 V;
+2 ... +15 mA
Input current at 24 V DC:
8 mA per input
Tightening torque
2
0.22 ... 0.25 Nm
(1.95 ... 2.2 lb−in)
2
4
Stripping length
5 mm for screw
connection
9 mm for spring
connection
2
.