Lenze ECSEE Serie Instructions De Montage page 58

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

2
Technical data
General data and operating conditions
General electrical data
EMC
Noise emission
Noise immunity
Insulation resistance
Discharge current to PE (acc. to
EN 61800−5−1)
Enclosure
Protective measures against
Protective insulation of control circuits Protective separation from the mains
1)
58
Compliance with the requirements acc. to EN 61800−3
Compliance with the limit class A acc. to EN 55011
(achieved by using collective filters typical for the application)
Requirements acc. to EN 61800−3
Requirement
1)
ESD
Conducted high
frequency
RF interference
(housing)
Burst
Surge (surge voltage on
mains cable)
Overvoltage category III acc. to VDE 0110
> 3.5 mA AC during operation
IP20 (NEMA 250 type 1) for
standard mounting (panel−mounted unit)
l
mounting in cold−plate technique
l
mounting with thermal separation (push−through technique), IP54
l
on heatsink side
Short circuit in power terminals (short−circuit−proof at mains
l
connection)
l
Short circuit in auxiliary circuits
– Digital outputs: short−circuit−proof
– System bus and encoder systems: partially short−circuit−proof
(corresponding monitoring functions can be deactivated, if
required.)
l
Earth fault (earth−fault protected at mains connection)
Overvoltage
l
Double/reinforced insulation acc. to EN 61800−5−1
The noise immunity with the severities given must be ensured by the control cabinet.
The user must check the compliance of the severities given.
Standard
EN 61000−4−2
EN 61000−4−6
EN 61000−4−3
EN 61000−4−4
EN 61000−4−5
l
Severity
3, i. e.
l
8 kV for air discharge
6 kV for contact
l
discharge
10 V; 0.15 ... 80 MHz
3, i. e. 10 V/m;
80 ... 1000 MHz
3/4, i. e. 2 kV/5 kHz
3, i. e. 1.2/50 ms
1 kV phase/phase
l
2 kV phase/PE
l
EDKCSEE040 DE/EN/FR 3.0