Mechanical installation
3.1
Important notes
Capacitor modules of series ECS feature enclosure IP20 and, for this reason,
ƒ
are intended for installation in control cabinets.
If the cooling air contains air pollutants (dust, fluff, grease, aggressive gases):
ƒ
–
Take suitable preventive measures , e.g. separate air duct, installation of
filters, regular cleaning.
Possible mounting positions
ƒ
–
Vertical on the mounting plate
–
DC−bus connections (X23) at the top
–
Connection for short−circuiting of the charging current limitation (X26) at
the bottom
Maintain the specified free spaces above and below to other installations!
ƒ
–
An additional free space is required if the shield assembly set
ECSZS000X0B001 is used.
–
Ensure unimpeded ventilation of cooling air and outlet of exhaust air.
–
You can install several modules of series ECS next to each other without
any clearance in a control cabinet.
The mounting plate of the control cabinet must be electrically conductive.
ƒ
In case of continuous vibrations or shocks use shock absorbers.
ƒ
EDKCSDK002 DE/EN/FR 1.1
Mechanical installation
l
Important notes
3