Error Warning - schmersal SD-I-U Serie Instructions De Montage

Masquer les pouces Voir aussi pour SD-I-U Serie:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Montage- und Anschlussanleitung / UNIVERSAL-Gateway für serielle Diagnose
Mounting and wiring instructions / UNIVERSAL gateway for serial diagnostics
Instructions de montage et de câblage / Passerelle UNIVERSEL pour diagnostic série
Table 2:
SD Master Diagnose, SD System error
english
Content Response byte 00, Diagnostic byte Gateway
The individual bits in the diagnostic byte for the SD-Gateway have the following meaning:
BIT
Error
Bit 0
Failure
Bit 1
Bit 2
Bit 3
Bit 4
SD initialisation error
Bit 5
SD Teach error
Bit 6
SD short circuit
Bit 7
SD communication error
Table 3: Status data of the SD slave
Content of the SD slave request byte
Always the 1st byte of an SD slave in the request
The individual bits in the request byte have the following meaning:
Request byte SD slave
Output byte PLC
device-specific,
Bit 0
e.g. solenoid interlocks AZM, MZM: „Magnet ON"
Bit 1
---
Bit 2
---
Bit 3
---
Bit 4
---
Bit 5
---
Bit 6
---
Bit 7
Error acknowledgment
Table 4: Diagnostic data of the SD slave
Always the 2nd byte of an SD slave in the response
Depending on the status of bit 6 (warning) and bit 7 (error) in the
response byte of the corresponding SD slave, the diagnostic byte
includes the following data:
Response byte
Bit 7
Bit 6
0
0
0
1
1
0
1
1
Description
SD Interface centralized alarm, message 1 sec. delayed, invalid SD data
Reinitialisation of the SD chain required! Shut down operating voltage of the
gateway and SD Slaves. Possibly no SD slave connected!
SD chain structure has changed after Power On! If OK, push TEACH
Bit 6 SD short circuit Short-circuit in the SD interface wires. Switch off and eliminate error.
One or more SD slaves unavailable. Invalid data from the SD slaves.
If necessary, check SD installation.
Content of the diagnostic byte
---
Warning message

(error warning)

Error message
(error)
Error message
(error)
Content of the SD slave response byte
Always the 1st byte of an SD slave in the response
The individual bits in the response byte have the following meaning:
Response byte SD slave
Input byte PLC
Bit 0
Safety outputs release
Bit 1
Actuator identified
Device-specific (refer to the
Bit 2
mounting instructions of the SD device)
Device-specific,
Bit 3
e.g. CSS 34F.: waiting for release or reset signal
Bit 4
Status inputs X1 AND X2
Device-specific (refer to the
Bit 5
mounting instructions of the SD device)
Bit 6
Error warning active
Bit 7
Error (enabling path switched off)
The individual bits in the diagnostic byte of the SD slave have the fol-
lowing meaning:
Bit
Error warning
Bit 0
Error output Y1
Bit 1
Error output Y2
Bit 2
Cross-wire short outputs
SD slave temperature
Bit 3
too high
Bit 4
---
Bit 5
Internal device error
SD communication error,
Bit 6
e.g. SD slave does not
respond
SD slave operating
Bit 7
voltage too low
SD-I-U-...
11 / 28
LED indication
SD (red) Teach (yellow)
ON
OFF/ON/Flash
ON
ON
ON
Flash
ON
OFF
ON
OFF
Error
Error output Y1
Error output Y2
Cross-wire short outputs
SD slave temperature
too high
Incorrect or
defective actuator
Internal device error
Device-specific (refer to
the mounting instructions
of the device)
---

Publicité

Table des Matières
loading

Table des Matières