Technical Data; Ul-Data; Standard Type; Ordering Example - DOLD BG 7926 Manuel D'utilisation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Technical Data

Time circuit
Release time:
Time accuracy:
Repeat accuracy:
Min. closing time:
Input
Nominal voltage U
:
N
Voltage range:
at 10 % residual ripple:
at 48 % residual ripple:
Nominal consumption
AC 24 V:
DC 24 V:
Nominal frequency:
Control current
AC 24 V:
DC 24 V:
Output
Contacts
BG 7926.60:
BG 7926.54:
The NO contacts are safety contacts
The NC contact 55-56 can only be used for monitoring.
Response time:
Release time:
Type of contact:
Nominal output voltage:
Thermal current I
:
th
Switching capacity
to AC 15
NO contact:
NC contact:
to DC 13
NO contact:
NC contact:
to DC 13
NO contact:
NC contact:
Electrical life
at 5 A, AC 230 V cos ϕ = 1:
Permissible switching
frequency:
Short circuit strength
max. fuse rating:
line circuit breaker:
Mechanical life:
General Data
Operating mode:
Temperature range
Operation:
Storage:
Altitude:
Clearance and creepage
distances
rated impulse voltage /
pollution degree:
EMC
Interference suppression:
Degree of protection
Housing:
Terminal plate:
Housing:
Vibration resistance:
Climate resistance:
1 s; 2 s; 3 s fixed
other times on request
30 %
± 5 % of nominal value
200 % of nominal value
AC/DC 24 V
AC 0.8 ... 1.1 U
N
DC 0.9 ... 1.1 U
N
DC 0.8 ... 1.1 U
N
2.1 VA
3 W
50 / 60 Hz
100 mA
120 mA
5 NO contacts,
1 NC contact for feedback circuit
4 NO contacts,
2 NC contacts for feedback and
indicator circuit
max. 20 ms
1 s, 2 s, 3 s
relay, forcibly guided
AC 250 V
max. 5 A
(see total current limit curve)
3 A / AC 230 V
IEC/EN 60 947-5-1
1 A / AC 230 V
IEC/EN 60 947-5-1
1 A / DC 24 V
IEC/EN 60 947-5-1
1 A / DC 24 V
IEC/EN 60 947-5-1
4 A / 24 V at 0.1 Hz
4 A / 24 V at 0.1 Hz
> 2 x 10
switching cycles
5
600 switching cycles / h
4 A gG / gL
IEC/EN 60 947-5-1
C8A
10 x 10
switching cycles
6
Continuous operation
- 15 ... + 55 °C
- 25 ... + 55 °C
< 2,000 m
4 kV / 2 (basis insulation) IEC 60 664-1
IEC/EN 62 061
Limit value class B
EN 55011
IP 40
IEC/EN 60 529
IP 20
IEC/EN 60 529
Thermoplastic with V0-behaviour
according to UL subject 94
Amplitude 0.35 mm
Frequenz 10 ... 55 Hz, IEC/EN 60 068-2-6
15 / 055 / 04
IEC/EN 60 068-1
Technical Data
Wire connection:
Wire connection:
Mounting:
Weight:
Dimensions
Width x height x depth:

UL-Data

The safety functions were not evaluated by UL. Listing is accom-
plished according to requirements of Standard UL 508, "general use
applications"
Nominal voltage U
:
N
Ambient temperature:
Switching capacity
NO contact :
NC contact:
Wire connection:
Technical data that is not stated in the UL-Data, can be found
in the technical data section.
nfo

Standard Type

BG 7926.60 3 s AC/DC 24 V 50/60 Hz
Article number:
• Output:
• Release time:
• Nominal voltage U
:
N
• Width:

Ordering Example

BG 7926 .60
3 s
AC/DC 24 V

Variant

BG 7926/61:
14
DIN 46 228-1/-2/-3
Plus-Minus terminal screws M3.5
Box terminals with wire protection
DIN rail
IEC/EN 60 715
180 g
22.5 x 84 x 121 mm
AC/DC 24 V
-15 ... +50°C
Pilot duty B300
5A 250Vac Resistive
5A 24Vdc Resistive or G.P.
5A 250Vac Resistive
5A 24Vdc Resistive or G.P.
60°C / 75°C copper conductors only
AWG 20 - 12 Sol Torque 0.8 Nm
AWG 20 - 14 Str Torque 0.8 Nm
0050808
5 NO contacts, 1 NC contact for feed
back circuit
3 s
AC/DC 24 V
22.5 mm
50 / 60 Hz
Nominal frequency
Nominal voltage
Release time
Contacts
Type
with UL-approval
BG 7926 / 31.05.21 en / 397A

Publicité

Table des Matières
loading