Approvals
(valid for marked equipment)
Construction
PY X-M-05-SSM + PY X-M-10-SSM: VdS 0786-CPD-21499
Product
Rated voltage
Regulation
(305/2011/EC )
Operating voltage range acc. to EN54-23
Lens colours
Signalling area
16
Environmental protection class
Installation position
Testing takes place using the supplied diaphragm nipple and the outer fastening bores.
PY X-M-05-SSM + PY X-M-10-SSM:
PY X-M-05-SSM + PY X-M-10-SSM:
VdS
Lens colours: White, yellow, amber, green, blue. These lens colors are not certified according to EN54-23 and are not be
used for alerting in case of fire.
PY X-M-xx + PY X-MA-xx
Rated Voltage
UL, cUL
Amb. Temp.
115V AC
230V AC
PYRA Xenon beacons PY X-M(A)-xx comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules.
Taking into Operation
Safety notes:
- Installation must be carried out by an electrician in compliance with the latest codes and regulations.
- Danger: High voltage may be present.
- Prior to opening, it must be ensured that no voltage is applied to the device.
- Before electrical connection, the supply voltage on the type plate is to be checked. The wrong operating voltage can lead to
damages or to the destruction of the equipment.
- During installation it must be ensured that the connection cables are secured against tension and distortion.
Please observe: The devices are not designed for portable use.
- CAUTION: When making installation, route field wiring away from sharp projections, corners and internal components.
- The function of the unit is only guaranteed if the upper and lower section is joined correctly.
- In order to prevent detriment to sight, continuously looking directly in the activated light is to be avoided.
- DC voltage: The device is provided with a reverse polarity protection. No function when polarity is reversed!
Opening the housing
1.
2.
3/8
The unit is not closed when delivered. Sealing plugs for the housing screws are available as accessories.
085 501 987j
Visual Signal Appliance - General Signaling Equipment (UEES, UEES7) (PY X-M-xx)
Audible and Visual Appliance for General Signaling (Non Fire Alarm) Use (UCST, UCST7 and UEES,
UEES7) (PY X-MA-xx)
115V AC or
230V AC or
12.5V DC – 48V DC (PY X-M-05 and PY X-M-10) / 24V AC (PY X-M-05 only) or
12.5V DC – 48V DC (PY X-MA-05 and PY X-MA-10) / 24V AC (PY X-MA-05 only) or
24V DC (PY X-M-05-SSM and PY X-M-10-SSM) or
24V DC (PY X-MA-05-SSM and PY X-MA-10-SSM)
-40°C .. +66°C
Suitable for indoor and outdoor use.
Warning: Not to be used as a Visual Public Mode Alarm Notification Appliance.(PY X-M-xx)
Warning: Not to be used as an Audible and Visual Public Mode Alarm Notification Appliance.(PY X-MA-xx)
According to CSA-C22.2 No. 205-12 clause 4.3.4 the connection is limited to max. six leads.
Installation:
The units shall be installed indoors or outdoors in accordance with the manufacturer's installation
instructions as well as the National Electrical Code (NFPA 70) in US. In Canada, they shall be installed in
accordance with the Canadian Electrical Code, Part 1. The installations shall also be in a manner
acceptable with the local authority having jurisdiction.
By loosening the four
cover screws, the upper
section can be re-
moved.
EN 54-23 Category O: see document 30360-005-1
G216036, data see Construction Product Regulation (305/2011/EC
G217037, data see Construction Product Regulation (305/2011/EC)
Closing the housing
1.
3/8
6
24V DC
18V – 30V DC (SSM)
red, clear , 0,5Hz, 0,75Hz, 1Hz
Type B
see document 30360-005-1
2.
The housing is closed by
turning the cover screws to
the limit position until the
housing locks into place.
30360-004-4j