Cleaning the condensate receptacle

Cleaning and refilling the syphon

Inspection of combustion chamber

1
3
5
22
Cleaning the condensate receptacle
2
Cleaning and refilling the syphon
Inspection of combustion chamber
The inspection opening is positioned on
the left hand side of the boiler.
6
7
Disconnect the plug of the fluegas
temperature sensor (1);
Remove the internal fluegas pipe (2)
of the boiler in order to create access
to the condensate receptacle;
Clean the receptacle (3);
Mount the fluegas pipe back in
position when the cleaning is finished;
Connect the plug of the fluegas
temperature sensor.
Remove the syphon (4) from the
condensate connection;
Clean and fill it with fresh water;
Mount the syphon back in the original
position.
Remove the radiation panel (5) from
the heat exchanger;
Remove the cover (6) from the
inspection opening;
Inspect the combustion chamber (7),
clean if necessary;
Mount the cover and radiation panel
back in original position.