Configuring Occupancy Sensor Settings (Optional) - Lutron GRAFIK Eye QSGRJ-3P Guide Rapide D'installation

Masquer les pouces Voir aussi pour GRAFIK Eye QSGRJ-3P:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Occupancy Sensor Setup (continued)

Configuring Occupancy Sensor Settings (optional)

Occupancy Sensor Settings
Main menu
Note: These settings affect all sensors assigned to the
Zone Setup
Grace Period: If the GRAFIK Eye QS control unit is transitioning to
Sensor Setup
an unoccupied state, motion detected within the grace period will
return the lights to the previously occupied level.
Range: 0 – 30 seconds* (default 15 seconds).
Sensor Setup
Vacancy Delay: An additional time delay after vacancy is detected
Daylight
and before unoccupied action occurs. Use when occupancy sensor
does not provide sufficient delay.
Occupancy
Range: 0 – 30 minutes (default 0 minutes).
Auto Turnoff: If lights assigned to an occupancy sensor are turned
on manually without the sensor reporting occupancy, the GRAFIK
Occ Sensor
Eye QS control unit can be set to automatically turn off the lights
after a set time delay. Disable this feature by setting the time delay
Settings
to 0 (disabled).
Range: Disabled or 1 – 30 minutes (default Disabled).
Diagnostics
Zone Fade: When in Zone Mode, lights can be set to fade to the
unoccupied levels over this period of time.
Range: 0 – 59 seconds; 1 – 10 minutes (default 10 seconds).
Settings
Configuring the Sensor Settings:
Auto Turnoff
1. Enter programming mode.
Zone Fade
2. Use the Master buttons to highlight "Sensor Setup" and press the
OK button to accept.
3. Use the Master buttons to highlight "Occupancy" and press the
Auto Turnoff
OK button to accept.
4. Use the Master buttons to highlight "Settings" and press the
5 minutes
OK button to accept.
5. Use the Master buttons to highlight the setting you wish to
configure. Press the OK button to accept.
6. Use the Master buttons to adjust the value of the selected setting.
Press the OK button to accept.
7. The info screen will confirm that your setting has been saved.
Saved
S aved
8. Exit programming mode.
GRAFIK Eye QS control unit.
For additional information, see the complete installation and operation guide at www.lutron.com/qs
GRAFIK Eye QS Control Unit Quick Installation and Operation Guide
OK
* Applicable only to units that ship with firmware version
8.027 and higher. Previous versions support settings
between 15 and 30 seconds.
Master