Zone Setup (continued)
Fixture load type
Incandescent
LED
MLV (magnetic low-voltage)
ELV (electronic low-voltage)
Hi-lume/Eco-10
0 –10 V
Zones
Non-dim lighting loads
1 – 6
Neon/Cold cathode
Tu-Wire
Advance Mark X
DMX
RGB/CMY DMX
Cree LR4/LR6 LED
* Use incandescent load type unless otherwise specified in the LED product selection tool available at
www.lutron.com/ledtool
Setting Load Types
Direct control via
Control via
GRAFIK Eye QS
power module
control unit
or interface
LUTRON
Choose this load type from the menu on the
GRAFIK Eye QS control unit:
Incandescent
Power module
LUTRON
Incandescent*
Power module
MLV
Power module
—
Power module
—
Fluorescent module
—
Fluorescent module
Non-dim
Non-dim
Neon, CC
Neon, CC
Tu-Wire
Tu-Wire
Tu-Wire
Tu-Wire
—
DMX
—
RGB/CMY DMX
Cree LR4/LR6 LED
Fluorescent module
For additional information, see the complete installation and operation guide at www.lutron.com/qs
GRAFIK Eye QS Control Unit Quick Installation and Operation Guide
Load Type Notes
• All electronic low-voltage (ELV) lighting
used with an interface must be rated for
reverse phase control dimming. Before
Power
LUTRON
installing an ELV light source, verify with the
module or
manufacturer that their transformer can be
interface
dimmed. When dimming, an ELV interface
(such as the PHPM-PA-DV-WH) must be
used with the control unit.
LUTRON
• For all DMX or RGB/CMY DMX lighting,
an external DMX interface (such as the
QSE-CI-DMX) must be used with the
control unit.
• Maximum total lighting load for Lutron
Tu-Wire and Advance Mark X electronic
dimming ballasts (120 to 127 V~ only)
must not exceed 6 A per zone or 16 A per
unit.
Zone ratings:
• Not all zones must be connected; however,
connected zones must have a minimum
load:
120 – 127 V~: 25 W
220 – 240 V~: 40 W
• Maximum zone loads:
120 – 127 V~: 800 W
220 – 240 V~: 1200 W
• Maximum total lighting load for magnetic
low-voltage (MLV) varies by input voltage:
120 – 127 V~: 800 VA / 600 W
220 – 240 V~: 1200 VA / 960 W
12