Take care!! Before starting on any
maintenance work, the roof extract fan
must be disconnected from the mains
voltage.
Dismantle the mounting plates(6) by
�
unscrewing the bolts(5);
Remove the top cover of the roof
�
extract fan(7) and the protective grille(1);
Check that the impeller and the base
�
are not dirty;
When cleaning any components, take
�
care not to damage the protective layer.
Take care!! The roof extract fan must
not be sprayed with water or with a high
pressure cleaner.
Dismantle the power cable of the motor
�
from the connection box or switch;
Dismantle the roof extract fan cover(3)
�
by pulling the hood up and at the same
time pushing out the clamp springs(2);
Dismantle the mounting plate(9) by
�
unscrewing the bolts(8);
When cleaning the parts, make sure not
�
to damage the antistatic coating.
Take note! Do not place with the impeller
on the ground!
5
6
8
9
4
10
Dismantle the carrier plate of the
�
impeller(14) by unscrewing the bolts(15);
Take the impeller off the hub of the
�
motor;
Put everything back in the reverse
�
order.
Take note! The marking on the impeller
must be located facing the key way of
the motor shaft, as this is the position in
which the impeller is balanced.
Check: The anti-static coating must not
�
be damaged or come loose from the fan
housing;
Check whether the impeller moves
�
freely;
Turn on the fan briefly to check which
�
way the impeller turns;
Check the impeller to ensure it is
�
balanced;
Check the bearings of the motor.
�
Take note! Carefully read the maintenance
instructions in the supplied instruction
manuals of the branching box, operating
switch and motor.