Under ceiling
installation
18
Please follow this below procedure for ceiling installation
Step
Action
1
The HCC 2 should always
tilt minimum 1° towards
the drain side(T4). This is
achieved when using the
enclosed bracket, placed at
T4 end of unit.
Drill two holes and mount
the bracket into the ceiling
configuration setup (see
page 17)
Please allow minimum 320
mm to the ceiling edge,
in order to have room for
turning the unit in step 2.
2
Lift the unit onto the
bracket hanging freely as
shown
3
Turn the unit towards the
ceiling, and secure it with
two screws
4
Connect ducts and drain hose.
Installation : Mounting
Illustration