Configuration Via Best Software - Bitzer CM-RC-01 Instructions De Montage

Masquer les pouces Voir aussi pour CM-RC-01:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Fig. 2: Updating the firmware
▶ Selection of B
LUETOOTH
A firmware update is not possible via the Bluetooth
interface.
All available devices are listed.
▶ Select compressor.
▶ Click on the C
ONNECT
▶ Enter the Bluetooth password. Factory setting from
firmware version 2.6.58.00:"8670", previous ver-
sions:"2".
➙ The compressor module is now connected to the PC
or mobile device.

5.1 Configuration via BEST SOFTWARE

Information
For further information on operating parameter
monitoring, electrical connection and communic-
ation via BEST SOFTWARE, see Technical In-
formation KT-230.
Configuration via BEST SOFTWARE (see figure 3,
page 29)
At least the following parameters need to be set / selec-
ted in the C
ONFIGURATION
• Compressor type.
• Refrigerants.
• Motor starter function.
• Serial number of the compressor.
Depending on the installed equipment, the following ad-
ditional parameters may have to be enabled:
• Type of start unloading.
KW-231-2
button.
menu:
• Additional fan.
• Liquid injection.
• CRII capacity control and the number of capacity
regulators installed.
• Monitoring of application limits.
• Low pressure and high pressure switches.
Once you have set all parameters, transfer the settings
to the device.
Fig. 3: Transferring user settings to the compressor module
29