UK: VACON
100 drive supply switch

3. Cable requirements

The following table shows the maximum sizes for the cables to be used with the drive supply switch.
NOTE! Use only copper cables with the drive supply switch option, no aluminium cables allowed!
Frame
Type
0003 2 - 0008 2
0011 2 - 0012 2
MR4
0003 5 - 0008 5
0009 5 - 0012 5
0018 2 - 0024 2
0031 2
0016 5 - 0023 5
MR5
0031 5
0004 6 - 0006 6
0009 6 - 0011 6
0048 2
0062 2
0038 5
0046 5
0061 5
MR6
0018 6 - 0027 6
0034 6
0007 7 - 0010 7
0013 7
0018 7 - 0027 7
0034 7
0075 2 - 0088 2
0105 2
0072 5 - 0087 5
0105 5
MR7
0041 6
0052 6 - 0062 6
0041 7
0052 7 - 0062 7
* Cables with heat resistance of at least +90°C must be used.
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Table 1. Cable data for the drive supply switch option
Maximum mains
and motor cable
2
size (mm
)
3 x 1.5 + 1.5
3 x 2.5 + 2.5
3 x 1.5 + 1.5
3 x 2.5 + 2.5
3 x 6 + 6
3 x 10 + 10
3 x 6 + 6
3 x 10 + 10
3 x 1.5 + 1.5
3 x 2.5 + 2.5
3 x 16 + 16
3 x 25 + 16
3 x 10 + 10
3 x 16 + 16
3 x 25 + 16
3 x 10 + 10
3 x 16 + 16
3 x 2.5 + 2.5
3 x 6 + 6
3 x 10 + 10
3 x 16 + 16
3 x 35 + 16
3 x 50 + 25*
3 x 35 + 16
3 x 50 + 25*
3 x 16 + 16
3 x 25 + 16
3 x 16 + 16
3 x 25 + 16
Tightening torque of
the drive supply
switch screws (Nm)
diameter/length (mm)
0.8
0.8
2
6
vacon • 9
Insulation tube size
for supply cable,
10/70
16/80
20/80
25/80
uk