4.1.2 ADDING SECTIONS
Add chimney sections, according to the manufacturers installation instructions. The chimney must extend at
least, 3 feet (1m) above its point of contact with the roof and at least 24 inches (61cm) higher than any wall,
EN
roof, building or obstacle within 10 feet (3m) horizontally.