3 Commissioning checklist
Work
93
Zone valve status
94
ZONE2
95
Zone activated
96
Day temperature
97
Set-back temp.
98
Room temperature
99
Zone assignment
100
Zone valve status
101
Domestic hot water
102
Cylinder active
103
Target flow temp.
104
Domestic hot water
105
Current cyl. temp.
106
Cyl. charging pump
107
Circulation pump
108
Anti-legionella day
109
Anti-legionella time
110
Cyl. boost hysteresis
111
Cylinder boost offset
112
Max. cyl. charg. time
113
DHW req. anti-cy time
114
Ch. pump overrun time
115
Parallel cyl. charging
Menu → Installer level → Service information
116
117
Enter contact details
118
Service date Next service on
→
End user menu
Menu → Basic settings → Enter zone name → ZONE1 → Change
119
Menu → Basic settings → Enter zone name → ZONE2 → Change
120
Menu → Desired temperatures → ZONE1
121
122
Day temp. heating
123
Day temp. cooling
124
Set-back temp. heat.
125
Room temperature
Menu → Time programmes → ZONE1
126
127
HEATING 1: Cooling
128
Domestic hot water
129
Circulation
6
Comments/settings
Current value display (closed/open)
Current value display: No / Yes
20 °C
15 °C
Current value display
VR91 ad.1
Current value display (closed/open)
Condition: Domestic hot water cylinder in the system
Current value display
60 °C
Inform the end user about the anti-legionella function
Current value display
Current value display: off / On
Current value display: off / On
–
Select: off, Monday, Tuesday, Wednesday,
Thursday, Friday, Saturday, Sunday, Monday -
Sunday
–
Factory setting: off
04:00
5 K
25 K
45 min.
30 min.
5 minutes
off
Telephone number/company
Maintenance interval: 1 year
Implement the settings for the end user/inform the end
user
Enter a suitable name for the zone, e.g. Flat 1
(In consultation with the customer)
Enter a suitable name for the zone, e.g. Flat 2
(In consultation with the customer)
Zone1 (name after being renamed)
20 °C
24 °C
15 °C
Current value display
Changed the time schedule for Zone 1 (name after being
renamed) following consultation with the customer
Zone 1 = heating circuit 1
change following consultation with the customer
change following consultation with the customer
change following consultation with the customer
System installation instructions 0020251826_01