Work
51
MA VR70, addr. 1
52
Heat pump 1
53
Status
54
Current flow temp.
55
Heat generator 2
56
Status
57
Current flow temp.
58
HEATING 1
59
Type of circuit
60
Status
61
Target flow temp.
62
Max limit outs.temp.
63
Heating curve
64
Minimum temperature
65
Maximum temperature
66
Auto Off mode
67
Cooling possible
68
Dew point monitoring
69
Min. cool. fl. tgt temp.
70
End OT cooling
71
Offset dew point
72
Pump status
73
HEATING 2
74
Type of circuit
75
Status
76
Target flow temp.
77
Current temperature
78
Excessive temp.
79
Max limit outs.temp.
80
Heating curve
81
Minimum temperature
82
Maximum temperature
83
Auto Off mode
84
Cooling possible
85
Pump status
86
Mixer status
87
ZONE1
88
Zone activated
89
Day temperature
90
Set-back temp.
91
Room temperature
92
Zone assignment
0020251826_01 System installation instructions
Commissioning checklist 3
Comments/settings
No funct.
Current value display (standby, heating, cooling, do-
mestic hot water)
Current value display
Current value display (standby, heating, cooling, do-
mestic hot water)
Current value display
Heating
Current value display (off, heating mode, cooling, do-
mestic hot water)
Current value display
21 °C, change in consultation with the customer, if re-
quired
0.4 to 0.6 for underfloor heating
15 °C
45 °C for underfloor heating
Set-back
Yes for underfloor heating
No; you should not use passive cooling for compact col-
lectors and flat collectors
Yes
18 °C
15 °C
2 K
Current value display: off / On
Heating
Current value display (off, heating mode, cooling, do-
mestic hot water)
Current value display
Current value display
21 °C, change in consultation with the customer, if re-
quired
–
0.4 to 0.6 for underfloor heating
–
max. 1.0 radiator heating
15 °C
–
45 °C for underfloor heating
–
55 °C for radiator heating
Set-back
No, with high-temperature heating circuit
Current value display: off / On
Current value display: Opening, Closing, Stationary
Current value display: No / Yes
20 °C
15 °C
Current value display
VRC 700
5