5. DRIVER BOX ELECTRICAL CONNECTIONS (CONT.)
Supply Power Wiring
The installer must provide a minimum Type SJ, 18 AWG 3-conductor supply power cord with ground.
Supply Power
AC Neutral (L2/N)
North America 100–120 V System
North America 208–240 V System
Australia
All Other Regions
Wired Wall Controller Wiring
Driver Box Terminal
Block
Driver Box Connectors
AC Line (L1)
Brown
Blue
Earth/PE
Green/Yellow
Black
Black, Red, or Blue
Brown or Red
Brown
1
White
Brown
3
Orange
Yellow
Blue
6
Green
7
Red
8
Black
Wired Wall Controller
AC Line (L1)
AC Neutral (L2/N)
White
Red, Blue, or Black
Black or Light Blue
Blue
Controller Input Cable
+0–10 VDC Speed Ref.
Not Used
Status LED (+)
Fire Alarm Shutdown (Closed: Fan Enabled, Open: Fan Disabled*)
Fire Alarm Shutdown (Closed: Fan Enabled, Open: Fan Disabled*)
Status LED (-)
+10 VDC Supply
DC Common
Green or Bare Copper
Green/Yellow
*To restart the fan, close the circuit and
turn off power to the fan for 60 seconds.
Fan
Earth/PE