4. Installation for EBM(s)
4.7
Connecting the EBM(s)
A small amount of arcing may occur when connecting an EBM to the UPS. This is normal and
will not harm personnel. Insert the EBM cable into the UPS battery connector quickly and firmly.
1. Plug the EBM power cable(s) into the battery connector(s). Up to 4 EBMs may be connected
to the UPS.
2. Verify that the EBM connections are tight and that adequate bend radius and strain relief exist for each
cable.
3. Connect the battery detection cable(s) to the connector of the UPS and of the EBM(s).
4. Check that the battery circuit breaker is switched to the "I" position (On).
4.8
Connecting other accessories
If you ordered other UPS accessories, refer to specific user manuals to check the connection
to the UPS.
Page 20
614-00205-01_EN