Power Cables Connection; Installation Requirements - Eaton 9PX8KSP Manuel D'installation Et D'utilisation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

5.1

Installation requirements

1. Recommended upstream protection
9PX 8K SP
9PX 10K SP
2. Recommended wire size
Terminal
position
L1
L2
N
Copper wire, solid or stranded.
614-00205-01_EN
UPS power rating
8000VA
10000VA
Wire
Terminal wire
function
size rating
Phase
8-4 AWG (10-25 mm
Phase
Neutral
Ground

5. Power cables connection

Upstream circuit breaker
D Curve - 60A
D Curve - 60A
Minimum input
wire size
)
6 AWG (75°C)
2
For 9PX 8K SP
4 AWG (75°C)
For 9PX 10K SP
Tightening
torque
18 lb in / 2.03 Nm
Page 21