Using The Device; Switching On The Device; Status Indications - Dometic SINEPOWER DSP 1212C Instructions De Montage Et De Service

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 67
SinePower
11

Using the device

11.1

Switching on the device

➤ Set the main switch (fig. 1 3, page 1) of the device to the "ON" position.
Set the On/Off switch to "OFF" to switch off.
➤ The device performs a self-test.
✓ After the self-test is completed successfully, the LED lights up blue (fig. 1 2,
page 1).
11.2

Status indications

The blue LED (fig. 1 2, page 1) shows the operating condition of the device.
Display
Constantly lit
Long flash, short interruption
Quick flash
Off
The device switches off if:
• The battery voltage drops below 10.5 V (12 Vg connection) or 21 V (24 Vg
connection).
• The battery voltage exceeds 16.5 V (12 Vg connection) or 33 V (24 Vg
connection).
• The device is overloaded.
• The device overheats.
• An overcurrent ocurs at the grid input.
➤ If this happens, shut down the device with the main switch (fig. 1 3, page 1).
➤ Check that the device is sufficiently ventilated and that the ventilation grilles are
unimpeded.
➤ Wait 5 – 10 minutes and switch the device on again without any electric
consumers.
EN
Input voltage
Normal mode
Device overheated/Overload
Overvoltage/Undervoltage
Other fault
Using the device
21