Les langues disponibles

Check: OK
The "SYSTEM STATUS" screen displays
all the system data on the CC Luxe.
System status
Inside temperature
Outside temperature
Bypass
GHE
Heater
ComfoCool
Filter remain
Comfo Control
Controller HR
2. Press "
" to return to the main
screen.
What to do in the event of a
malfunction
When an malfunction occurs, please
contact the fitter.
� Make a note of your ventilation system
type.
� Make a note of any malfunction codes
on the CC Luxe display.
The system should remain connected to
its power supply unless the ventilation
unit requires taking out of service due to a
serious malfunction or for filter cleaning/
replacement or any other compelling
reasons.
When the unit is unplugged, the dwelling
will no longer benefit from mechanical
ventilation, and this can lead to problems
with damp and mould. Long-term
deactivation of the ventilation unit must
therefore be prevented.
Wednesday
Cooker hood
Settings
1
GHE
2
21ºc
15ºc
losed
Open
Not installed
Not installed
3 wks
Rev. 3.007B1.007
Rev. 0.000
Meaning of the error messages
Code
Description
A0
NTC sensor Tge is faulty.
(= Temperature of the outside air for base
exchanger)
A1
NTC sensor T1 is faulty.
(= Temperature of the intake air)
A2
NTC sensor T2 is faulty.
(= Temperature of the supply air)
A3
NTC sensor T3 is faulty.
(= Temperature of the extract air)
A4
NTC sensor T4 is faulty.
(= Temperature of the exhaust air)
A5
Malfunction in the bypass
motor.
A6
Malfunction in the motor of the preheater
element
A7
Preheater element not heating sufficiently.
A8
Preheater element becomes too hot.
A10
NTC sensor Tch is faulty.
(= Temperature in the ComfoHood)
A11
NTC sensor Tah is faulty.
(= Temperature of the reheater)
E1
Extract fan not rotating.
E2
Supply fan not rotating.
E3
Temperature sensor ComfoHood too high.
E4
The ventilation unit has been switched off
by external contact
EA1
Enthalpy sensor measures excessively
high Relative Humidity (RH) values.
EA2
The ventilation unit is not
communicating with the enthalpy sensor.
EA15
The ventilation unit is not communicating
with the CC Luxe.
EA16
CC Luxe is not communicating with the
ComfoCool
Filter
Filter is dirty
C1
Condenser of the ComfoCool becomes
too hot.
C2
Compressor of the ComfoCool is faulty.
C3
NTC sensor Tcon of the
ComfoCool is faulty.
(= Temperature of the condenser)
C4
NTC sensor Tin of the ComfoCool is faulty.
(= Temperature of the supply air)