Safety Guidelines; Description Of Function; Technical Data - Honeywell F78TS Notice De Montage

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 10

1. Safety Guidelines

1. Follow the installation instructions.
2. Use the appliance
• according to its intended use
• in good condition
• with due regard to safety and risk of danger.
3. Note that the appliance is exclusively for use in the
applications detailed in these installation instructions. Any
other use will not be considered to comply with
requirements and would invalidate the warranty.
4. Please take note that any assembly, commissioning,
servicing and adjustment work may only be carried out by
authorized persons.
5. Immediately rectify any malfunctions which may influence
safety.

2. Description of function

The filter insert is divided into two parts. In the „filtering"
position, only the lower, larger section is used for filtering. The
small upper section does not come in contact with unfiltered
water. An oscillating flap integrated in the sieve prevents the
deposition of dirt particles on the upper part of the filter.
When the ball valve is opened for reverse rinsing, then the
whole filter insert is pushed downwards until the water supply
to the outer side of the main filter is stopped. Simultaneously,
the water flow is opened to the upper part of the filter. The
water needed for cleaning the filter passes through the upper
filter section, then the rotating impeller with jets and the main
filter from inside to outside, i.e. the filter is reverse rinsed with
filtered water. The filter automatically switches back to the
operating position when the ball valve is closed again.
7. Dimensions and Flow Values
Connection size
Weight
Dimensions
Flow value at
Δp = 0.2 bar
Δp = 0.5 bar
k
-value
vs
DIN/DVGW Registration No.
Flow Diagram see page 8
Honeywell GmbH
DN
65
approx. kg
25
mm
L
290
H
581
h
434
D
193
F
185
m
/h
3
30
48
69
GB
3. Application
Medium
The filter is constructed for drinking water installations. In case of a
process water application the filter has to be proven individually.

4. Technical data

Installation position
Nominal pressure
Operating pressure
Operating temperature Max. 40°C
Connection size
Single filter
2 filters parallel
5. Scope of delivery
The fine filter comprises:
• Housing with pressure gauge ports (1x inlet, 2x outlet)
• 2 pressure gauges (1x inlet, 1x outlet including memory
indicator)
• PN 16 flanges to EN 1092-2
• Fine filter
• Filter bowl
• Ball valve with lever and drain funnel
6. Options
Filter mesh size 100 μm
F78TS-...FA =
Filter mesh size 20 μm
F78TS-...FB =
Filter mesh size 50 μm
F78TS-...FC =
Filter mesh size 200 μm
F78TS-...FD =
Connection size DN65/80/100
F78TS-125ZFA = Filter mesh size 100 μm
Single filter
80
100
35
43
310
350
665
767
508
610
230
247
200
220
48
60
78
100
113
145
requested
6
Water
Horizontal, with filter bowl
downwards
PN16
Min. 1.5 bar
Max. 16.0 bar
Max. 65°C (max. operating pressure
6.0 bar)
DN 65 - DN 125
2 x DN80
2 x DN100
2 filters parallel
125
80
65
n.a.
514
n.a.
767
n.a.
610
n.a.
247
n.a.
250
n.a.
60
96
100
156
145
226
-
-
MU1H-1178GE23 R0816
100
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
120
200
290
-

Publicité

Table des Matières
loading

Table des Matières