1. Safety Guidelines

1. Follow the installation instruc-
tions.
2. Use the appliance
• according to its intended use
• in good condition
• with due regard to safety and
risk of danger.
3. Note that the appliance is exclu-
sively for use in the applications
detailed in these installation
instructions. Any other use will
not be considered to comply
with requirements and would
invalidate the warranty.
4. Please take note that any
assembly, commissioning,
servicing and adjustment work
may only be carried out by
authorized persons.
5. Immediately rectify any
malfunctions which may influ-
ence safety.

2. Functional description

The temperature relief valve is
actuated by the flow temperature
of the heat generator. It comprises
a spring-loaded valve and a
bellows operated temperature
sensor. When a boiler flow tempe-
rature of 95ºC is reached the force
exerted by the bellows system
MU1H-1543GE23 R0709
GB
becomes greater than the force of
the spring and the valve opens.
Heated potable water then flows
out and this is replaced by cold
water from the supply network.
This absorbs excess heat from the
heat generator and prevents over-
heating.

3. Application

Multi-fuel boilers with integral
water heating or condensing coils
in closed solid-fuel fired heating
systems to EN 12828.

4. Technical data

Heating system
capacity
Opening
temperature
Flow capacity 2800 kg/h water at
Connection
size
Operating pres-
sure

5. Scope of delivery

The temperature relief valve
comprises:
• Housing with internal thread
7
max. 100 kW
95 °C
the pressure drop
∆p=1 bar (Inlet
pressure 5bar;
Outlet pressure
4bar) (1 capillary
tube)
Rp
/
"
3
4
(DIN EN 10226)
max. 5 bar