3. Maintenance
Planned maintenance is recommended
and DIN 1988, Part 8 specifies the
following operations:
The filter must be cleaned regularly by
reverse rinsing and at intervals of no
longer than two months. This operation
can be carried out by the user.
Filter can become blocked if this is not
done, resulting in pressure drop and
falling flow rate
The filter sieves are stainless steel.
Red rust deposits from the pipework
have no effect on function and filter
operation.

4. Scope of Application

Connection sizes
½" to 2"
With Clear Filter Bowl
Medium
Water up to maximum 40 °C
Operating
pressure
min. 1.5 bar, max 16.0 bar
Do not use any cleaning materials
containing solvents for cleaning
plastic parts.
Use a red-bronze filter bowl in
locations where ultra violet rays or
solvent fumes are present.
With Red-bronze Filter Bowl
Medium
Water up to maximum 70 °C
Operating
pressure
min 1.5 bar, max 25.0 bar
GB

5. Safety Guidelines

1. Use the appliance
In good condition
According to regulations
With due regard to safety
2. Follow installation instructions
3. Immediately rectify any malfunctions
which may influence safety.
4. The HABEDO
©
retrofit filter is exclusively
for use for applications detailed in these
installation instructions. Any variation
from this or other use will not comply
with requirements.