Victron energy BMV-600S Manuel page 16

Masquer les pouces Voir aussi pour BMV-600S:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 47
SYNC: Manual synchronization. This option can be used to manually synchronise the
BMV.
R DEF: Reset to factory defaults. Resets all settings to factory default by holding the
select button for 3 seconds.
Cl HIS: Clear historic data. Clears all historical data by holding the select button for 5
seconds.
Lock: Setup lock. When on, all settings (except this one) are locked and cannot be
altered.
Firmware version (cannot be altered).
SW:
BMV-602S ONLY
AlS:
Alarm low starter battery voltage. When the starter battery voltage falls below this
value for more than 10 seconds the low starter battery voltage alarm is turned on.
This is a visual and audible alarm. It does not activate the relay.
AlSc: Clear low starter battery voltage alarm. When the starter battery voltage rises
above this value, the alarm is turned off. This value needs to be greater than or
equal to AlS.
AhS:
Alarm high starter battery voltage. When the starter battery voltage rises above
this value for more than 10 seconds the high starter battery voltage alarm is turned
on. This is a visual and audible alarm. It does not activate the relay.
AhSc: Clear high starter battery voltage alarm. When the starter battery voltage falls
below this value, the alarm is turned off. This value needs to be less than or equal to
AhS.
RlS:
Relay low starter battery voltage. When the starter battery voltage falls below this
value for more than 10 seconds the relay will be activated.
RlSc: Clear relay low starter battery voltage. When the starter battery voltage rises
above this value, the relay will be de-activated. This value needs to be greater than
or equal to RlS.
RhS: Relay high starter battery voltage. When the starter battery voltage rises above
this value for more than 10 seconds the relay will be activated.
RhSc: Clear relay high starter battery voltage. When the starter battery voltage falls
below this value, the relay will be de-activated. This value needs to be less than or
equal to RhS.
D VS: Starter battery voltage display. Should be ON to display starter battery voltage in
the monitoring menu.
12

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Bmv-600hsBmv-602s

Table des Matières