Gas Connections - Modine HDS Serie Manuel D'installation Et D'entretien

Masquer les pouces Voir aussi pour HDS Serie:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

InsTAllATIon - gAs ConneCTIons

gAs ConneCTIons

WARNING
1. All field gas piping must be pressure/leak tested prior to
operation. Never use an open flame. Use a soap solution
or equilavent for testing.
2. Gas pressure to appliance controls must never exceed 14"
W.C. (1/2 psi).
3. To reduce the opportunity for condensation, the minimum sea
level input to the appliance, as indicated on the serial plate,
must not be less than 5% below the rated input, or 5% below the
minimum rated input of dual rated units.
cAUTION
1. Purging of air from gas lines should be performed as
described in ANSI Z223.1 - latest edition "National Fuel
Gas Code", or in Canada CSA-B149 codes.
2. When leak testing the gas supply piping system, the
appliance and its combination gas control must be isolated
during any pressure testing in excess of 14" W.C. (1/2 psi).
3. The unit should be isolated from the gas supply piping
system by closing its field installed manual shut-off
valve.This manual shut-off valve should be located within
6' of the heater.
4. Turn off all gas before installing appliance.
IMPORTANT
To prevent premature heat exchanger failure, the input to the
appliance, as indicated on the serial plate, must not exceed
the rated input by more than 5%.
1. Installation of piping must conform with local building codes,
or in the absence of local codes, with the National Fuel Gas
Code, ANSI Z223.1 (NFPA 54) - latest Edition. In Canada,
installation must be in accordance with CSA-B149.1.
2. Piping to units should conform with local and national
requirements for type and volume of gas handled, and
pressure drop allowed in the line.Refer to Table 12.1 to
determine the cubic feet per hour (CFH) for the type of gas
and size of unit to be installed. Using this CFH value and the
length of pipe necessary, determine the pipe diameter from
Table 12.2. Where several units are served by the same
main, the total capacity, CFH and length of main must be
considered. Avoid pipe sizes smaller than 1/2". Table 12.2
allows for a 0.3" W.C. pressure drop in the supply pressure
from the building main to the unit. The inlet pressure to the
unit must be 6-7" W.C. for natural gas and 11-14" W.C. for
propane gas. When sizing the inlet gas pipe diameter, make
sure that the unit supply pressure can be met after the 0.3"
W.C. has been subtracted. If the 0.3" W.C. pressure drop is
too high, refer to the Gas Engineer's Handbook for other gas
pipe capacities.
3. Install a ground joint union with brass seat and a manual
shut-off valve adjacent to the unit for emergency shut-off
and easy servicing of controls, including a 1/8" NPT plugged
tapping accessible for test gauge connection (See Figure 12.1).
4. Provide a sediment trap before each unit in the line where
low spots cannot be avoided. (See Figure 12.1).
5. When Pressure/Leak testing, pressures above 14" W.C.
(1/2 psi), close the field installed shut-off valve, disconnect
the appliance and its combination gas control from the gas
supply line, and plug the supply line before testing. When
testing pressures 14" W.C. (1/2 psi) or below, close the
manual shut-off valve on the appliance before testing.
12
figure 12.1 - recommended sediment Trap/manual
shut-off valve Installation - side or Bottom gas
Connection
GAS
SUPPLY LINE
GROUND
MANUAL
JOINT
SHUT-OFF
UNION
VALVE
GAS
SUPPLY LINE
PLUGGED
3"
1/8" NPT TEST
MIN.
GAGE CONNECTION
SEDIMENT
TRAP
Manual shut-off valve is in the "OFF" position when handle is perpendicular to pipe.
Table 12.1 - manifold pressure & gas Consumption
model
BTu/Cu. ft.
size
specific gravity
manifold pressure In. W.C.
CFH
Gal/Hr. Propane
30
Sec/cu. ft.
Orifice Drill Size
CFH
Gal/Hr. Propane
45
Sec/cu. ft.
Orifice Drill Size
CFH
Gal/Hr. Propane
0
Sec/cu. ft.
Orifice Drill Size
CFH
Gal/Hr. Propane
75
Sec/cu. ft.
Orifice Drill Size
CFH
Gal/Hr.Propane
100
Sec/cu.ft.
Orifice Drill Size
CFH
Gal/Hr.Propane
125
Sec/cu.ft.
Orifice Drill Size
Table 12.2 - gas pipe Capacities - natural gas
Pipe
Length (ft)
1/2"
3/4"
10
132
278
20
92
190
30
73
152
40
63
130
50
56
115
60
50
105
70
46
96
80
43
90
100
38
79
125
34
72
150
31
64
Capacities in Cubic Feet per Hour through Schedule 40 pipe with maximum
0.3"W.C. pressure drop with up to 14"W.C. gas pressure. Specific graivity is 0.60
for Natural gas and 1.50 for Propane gas.
For Pipe Capacity with Propane Gas, divide Natural gas capacity by 1.6. Example:
What is the propane gas pipe capacity for 60 feet of 1-1/4" pipe? The Natural gas
capacity is 400 CFH. Divide by 1.6 to get 250 CFH for Propane gas.
6-584.2
TO
CONTROLS
natural
propane
1050
2500
no. of
0.0
1.53
orifices
3.5
10.0
28.6
12.0
2
.33
126
300
49
56
42.9
18.0
3
.50
84
200
49
56
57.1
24.0
4
.66
63
150
49
56
71.4
30.0
5
.83
50
180
49
56
95.2
40
5
1.09
38
90
45
55
119
50
5
1.37
30
72
42
53
Natural Gas
1"
1-1/4" 1-1/2"
2"
520
1050
1600
3050
350
730
1100
2100
285
590
890
1650
245
500
760
1450
215
440
670
1270
195
400
610
1150
180
370
560
1050
170
350
530
930
150
305
460
870
130
275
410
780
120
250
380
710
➀ ➁

Publicité

Chapitres

Table des Matières
loading

Table des Matières