COMMISSIONING
6 Press " " or " ", select "LOUV." and select "
by pressing " " or " ". The auto swing operation will be started.
Check the operating sound at the louvers. If abnormal sound
is not generated, press " " or " " again to stop the auto swing
operation.
7 The temperature detections by the thermistors are invalid though the protection devices are valid during the test run.
8 For SET-FREE Series: According to the label "Checking of Outdoor Unit by 7-Segment Display on PCB1" attached to the rear
side of the front cover of the outdoor unit, check temperature, pressure and the operation frequency, and connected indoor unit
numbers by 7-segment displays.
9 To finish the test run, press " " (run/stop) again or pass over the
set test run time. When changing the test run time, press " " or
" " to select "T-RUN TIME". Then, set the test run time (30 to 600
minutes) by pressing " " or " "
The RUN indicator on the remote control switch flashes when
•
some abnormalities such as protection devices activated occur
during the test run as well as the RUN indicator (orange) on
the indoor unit flashes (0.5 second ON/ 0.5 second OFF).
Additionally, the alarm code, the unit model code and connected
number of indoor units will be displayed on the LCD as
shown in the figure below. If the RUN indicator on PC-ARFPE
flashes (2 seconds ON/ 2 seconds OFF), it may be a failure
in the transmission between the indoor unit and the remote
control switch (loosening of connector, disconnecting wiring or
breaking wire, etc.). Consult to authorized service engineers if
abnormality can not be recovered.
17
PMML0389B rev.1 - 07/2016
" (auto swing)
Refrigerant Cycle No.
of Indoor Unit which
Abnormality Occurs
Unit Model Code
Test Run: 2 units
COOL
MODE
HIGH
SPEED
LOUV.
T-RUN TIME 120MIN
SEL.
ADJ
STOP
Test Run: 2 units
MODE
COOL
SPEED
MED
LOUV.
T-RUN TIME
510MIN
SEL.
ADJ
STOP
01-02
22
Alarm Code:
MODEL : b .02
SEL.
OP MODE
ENT.
OK
Indoor Unit No.
which Abnormality Occurs
01 - 02
22
Alarm Code:
Alarm Code No.
MODEL : b . 02
Total No. of Indoor Unit in
Same Refrigerant Cycle as
One that Abnormality Occurs
ALM RST
ADDR