Commissioning - Buderus EM100 Instructions D'installation

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

120/230VAC 120/230VAC
230 VAC
Caption to the figure above and connection diagrams with
system schematics at end of document:
Protective conductor
Connecting terminal designations:
230 V AC
Mains voltage connection
BUS
BUS system connection
BMS
Building Management System with 0-10 V
interface
HS
Heat Source on BUS system
OE1-74
Mains voltage output, solenoid valve
OE1-75
Fault output (230 V)
PC0
Mains voltage output, pump (230 V)
IE0
Pump alarm output
(default setting: N/O contact)
OP0
Pump on/off
(output/potential-free contact ≤ 24 V),
coding position 3‒5: potential-free fault output
T0
Low loss header temperature sensor input
IO1-1(+),2(-) Feedback output for heat source power
(0-10 V)
IO1-3(+),4(-) Input for heat source activation
(setpoint value 0–10 V)
OC0 1-2
Output for pump control signal
(setpoint value 0-10 V/PWM)
OC0 1-3
Pump feedback input (pulse width modulation),
2)
optional
CON
Control unit with BUS system (Controller)
MC
Boiler control device (Master Controller)
MM 100
Heating circuit module (EMS/EMS plus)
EM100
Extension module
1) With the heat exchanger, T0 is the flow temperature sensor.
2) Observe coding switch position.
EM100 – 6721804147 (2019/10)
EM100
120/230 V AC
OE1
PC0
N L
N
L
N 74
75
N 63
N
L
N L
M
PC0
230 VAC
OE1
OE1
2)
≤ 24 V
IO1
OC0
3
1
2
3
4 1
2 3
2
1
0
≤ 24 V
IE0 OP0
T0
BUS
1 2 1 2
1 2
1 2
1 2
(+) (–)
IO1
IE0
OP0
T0
BUS
0-10 V 0-10 V
4

Commissioning

First make all electrical connections and then carry out the
commissioning!
▶ Observe the installation instructions for all components
and assemblies in the system.
▶ Only switch on the power supply if the coding switch is set up.
▶ If a control unit is connected, it is recommended to start the
configuration wizard.
NOTICE:
Risk of damage to system through pump failure!
▶ Fill and vent the system before switching it on so that the
1)
pumps do not run dry.
4 5 6
4 5 6
7
3
7
2
8
9
1
9
10
10
0
OC0
1
2
3
3 4
1 2 3
1 2
3
(+) (–)
0-10V
PWM
IO1
OC0
OC0
8
0010029500-001
21