Specification
Rated voltages
•
BUS
•
Module mains voltage
•
User interface
•
Pump, solenoid valve,
interference output
Fuse
BUS interface
Power consumption – Standby < 3 W
Max. power output
•
per connection(PC0)
•
per connection(OE1)
Permitted ambient
temperature
IP rating
Protection class
ID no.
Temperature of ball thrust test 75 °C
Degree of pollution
Table 3
°C
°C
20
12486
50
25
10000
55
30
8060
60
35
6536
65
40
5331
70
45
4372
75
Table 4
Measurements of low loss header temperature
sensor (T0)
18
•
15 V DC
(reverse polarity
protected)
•
230 V AC, 50 Hz
•
15 V DC
(reverse polarity
protected)
•
230 V AC, 50 Hz
230 V, 5 AT
EMS and EMS plus
•
400 W (high-efficiency
pumps permissible:
< 30 A for 10 ms)
•
120 W (high-efficiency
pumps permissible:
< 30 A for 10 ms)
0 ... 60 °C
IP 44
I
Data plate ( Fig. 21 at the
end of document)
2
°C
3605
80
1256
2989
85
1070
2490
90
915
2084
100
677
1753
–
–
1480
–
–
2.5
Additional accessories
For detailed information about suitable accessories, refer to
the catalogue or Internet page of the manufacturer.
•
Low loss header temperature sensor; connection to T0
•
Primary pump; connection to PC0
Installation of additional accessories
▶ Install the additional accessories in accordance with legal
regulations and the instructions supplied.
2.6
Cleaning
▶ Wipe the casing with a damp cloth when necessary. Never
use aggressive or caustic cleaning agents for this.
3
Installation
DANGER:
Danger to life from electric shock!
Touching live electrical parts can cause an electric shock.
▶ Before installing this product: Disconnect the heat source
and all other BUS nodes from the mains voltage across all
poles.
▶ Before commissioning: Mount the cover ( Fig. 20 at end
of document).
3.1
Preparation for the installation in the heat
source
▶ Check by referring to the installation instructions of the
heat source whether it is possible to install modules (e.g.
EM100) in the heat source.
▶ If the module can be installed in the heat source without a
mounting rail, prepare the module ( Fig. 8 and 9 at end
of document).
3.2
Installation locations
▶ Install the module on a wall, ( Fig. 10 and 11 at end of
document), on a mounting rail ( Fig. 12 at end of
document), in an assembly or in the heat source.
▶ When the module is installed in a heat source, observe the
heat source instructions.
▶ Remove the module from the mounting rail ( Fig. 13 at
end of document).
EM100 – 6721804147 (2019/10)