ACCESSORIES
Programming key [ code QUIXPRG ]
Programming key: Use method
- Parameter transmission from the key to the inverter:
- plug the key into the suitable connector ( see page 36)
- select, via the keypad, the C - 04 parameter, choose the code 7 and press E
If the key contains invalid parameters, the factory-preset parameters will be used and the message " Err", will be displayed for
4 sec. Otherwise, data will be permanently stored and the confirmation message " done" will be displayed for 2 sec.
- Parameter transmission from the inverter to the key:
- plug the key into the suitable connector ( see page 36)
- select, via the keypad, the C - 05 parameter, choose the code 7 and press E
If the key is write-protected, the control is interrupted and the message " off" is displayed for 4 sec. Otherwise, the inverter pa-
rameters are stored on the key and, at the end of the operation, the message " done" will be displayed for 2 sec. to confirm the
operation.
Remote terminal [ code QUIXREM ]
105 (4,13")
90 (3,54")
Regolazione contrasto display LCD
LCD contrast adjustment
PWR
FWD
REV
PRG
M
E
STOP
FWD
JOG
1 2 3 4
- Wiring the Remote Terminal:
Correspondence between the terminals of the Remote Terminal and those of the inverter control circuit:
Remote terminal
24 Vdc 1
LNK+
2
LNK-
3
GND
4
The inverter and remote terminal factory-preset parameters are in a position to grant the correct link working.
34-GB
The data are stored in a E
necessary.
The switch put on the key upper front side allows to protect the stored
data against possible writing procedures. To copy the data from an inverter
to the key or viceversa the keypad panels are used.
PRG
RESET
REV
shield
1
—————— SIEI ——————
The programming key device allows to transfer parameters from and
to the QUIXDrive inverter or between inverters.
2
The remote terminal allows the connection to the inverter, QUIXDrive single
phase series, through a 2-wire RS 485 serial line with a programmable Baud
Rate.
The serial connection allows the remote terminal to control up to 32 inverter.
The remote terminal supply needs +8/+24 Vdc, available on the terminal
board .
Operator interface :
- 16 character LCD alphanumeric display, possibly backlighted.
- 8 keys to program and control the inverter. The STOP, FWD, JOG,
and REW keys performs the direct operation of run and stop of an
inverter enabled to do so.
- 4 signalling Led .
A 4-wire terminal block is provided to link the remote terminal to
inverters .
(For the detailed instructions see the specific handbook)
QUIXDrive inverter terminals
1 1
PROM type memory, so battery backup is not
6
8
9
7