6.
Installation
6.4

Mounting the optosensors

(optional)

6.4.1
Preparation
6.4.1 / 1
The bottom door seals must be adjusted to
ensure that the optosensors do not overhang.
• Cut back the bottom door seals on both sides
as necessary.
The system cable (E) and the vent hose (F) must
be laid in the upper chamber.
• Cut out the bottom door seal on both sides as
necessary.
66
3
6
10
10
Manual for installation and operation, Special 802, 803 GB (#81811)
Advice:
For the "one side" connection unit
model, the transmitter with the long
connection cable is fed through the
bottom door seal and connected to
the housing connection unit.
For the "both sides" connection unit
model, the receiver and transmitter
are each connected to the relevant
housing units. The housing units are
connected using a connection cable,
included in the package, which is fed
through the bottom door seal.