Alarms Menu; Config Menu - Carrier HSM Manuel D'utilisation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

4.9.5 - RUnTIMe menu
Point
Description
hrhppmp
Number of operating hours, external pump
hrhl1pmp
Number of operating hours, loop 1
hrhl2pmp
Number of operating hours, loop 2
hrdhwpmp
Number of operating hours, DHW pump
hr_hp
Number of operating hours, heat pump
hr_bckup
Number of operating hours, back-up heating

4.9.6 - ALARMS menu

Item
Description
ALRMMENU
Alarm initialisation
4.9.6.1 - ALARMRST sub-menu
Point
Description
RST_ALM
Alarm reset
ALM
Alarm status
alarm_1c
Current alarm 1
alarm_2c
Current alarm 2
alarm_3c
Current alarm 3
alarm_4c
Current alarm 4
alarm_5c
Current alarm 5

4.9.7 - COnFIG menu

Item
Description
GEN_CONF General configuration menu
PUMPCONF Pump configuration menu
HL1_CONF
Configuration menu, loop 1
HL2_CONF
Configuration menu, loop 2
DHW_CONF DHW configuration menu
BKUPCONF Back-up heating configuration menu
DIS_CONF
District heating configuration menu
USERCONF User configuration menu
DATETIME
Time control
DISPLAY
Parameter display
CTRL_ID
Control identification
FACTORY
Factory parameters
4.9.7.1 - Gen_COnF sub-menu
Point
Description
hp_add
Heat pump CCN address
oat_add OAT sensor CCN address
hp_bias
Heat pump correction control point 0.0 to 4.0
sani_dur Duration, anti-legionella treatment 0 to 120
sani_day Anti-legionella treatment days
sani_hr
Anti-legionella treatment time
Notes Description
1
0 = Local sensor connected to the HSM
1 to 240 = CCN address of the heat pump, where the OAT is read
255 = No sensor
2
The logic board is rebooted after changing this parameter.
3
b7
b6
b5
b4
b7: Monday
b6: Tuesday
b5: Wednesday
b4: Thursday
b3: Friday
b2: Saturday
b1: Sunday
b0: Not used
4.9.7.2 - PUMPCOnF sub-menu
Point
Description
hppmp_s
External pump anti-stick function
hppmpsby Pump stop when heat pump is in standby No/Yes
hl1pmp_s
Pump anti-stick function, loop 1
hl2pmp_s
Pump anti-stick function, loop 2
dhwpmp_s DHW Pump anti-stick function
en
8
ENGLISH
Format
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
nnnnn
Format
Yes/No
nnn
nnn
nnn
nnn
nnn
Format
Default
0 to 240
1
0 to 225
0
1
0.0
30
2
bbbbbbbb
10000000
0 to 23
12
b3
b2
b1
b0
Format
Default Units
No/Yes
Yes
No
No/Yes
Yes
No/Yes
Yes
No/Yes
Yes
4.9.7.3 - HL1_COnF sub-menu
Point
Description
Units
starttmr
Time before pump start-up, loop
Hours
stop_tmr Time before pump stop, loop
Hours
oat_ctrl
Control point based on outside air
Hours
temperature
Hours
curvpnt1 Climate curve: OAT point -36°C
Hours
curvpnt2 Climate curve: OAT point -27°C
Hours
curvpnt3 Climate curve: OAT point -18°C
curvpnt4 Climate curve: OAT point -9°C
curvpnt5 Climate curve: OAT point 0°C
curvpnt6 Climate curve: OAT point 9°C
curvpnt7 Climate curve: OAT point 18°C
curvpnt8 Climate curve: OAT point 27°C
Note
Description
1
The logic board is rebooted after changing this parameter.
Units
-
-
4.9.7.4 - HL2_COnF sub-menu
-
Point
Description
-
hl2_kp
Mixing valve proportional gain
-
hl2_ki
Mixing valve integral gain
-
hl2_bias Control point correction
-
Oat_ctrl
Control point based on the outside
temperature
curvpnt1 Climate curve: OAT point -36°C
curvpnt2 Climate curve: OAT point -27°C
curvpnt3 Climate curve: OAT point -18°C
curvpnt4 Climate curve: OAT point -9°C
curvpnt5 Climate curve: OAT point 0°C
curvpnt6 Climate curve: OAT point 9°C
curvpnt7 Climate curve: OAT point 18°C
curvpnt8 Climate curve: OAT point 27°C
4.9.7.5 - BKUPCOnF sub-menu
Point
Description
bck_pull Heat pump temperature pulldown time
hp_start Heat pump start-up time
htr_kp
Electric heater proportional gain
htr_ki
Electric heater integral gain
mix_kp
Mixing valve proportional gain
mix_ki
Mixing valve integral gain
Units
bck_fail
Back-up for fault GT1
-
hl2_fail
HL2 cmd for fault GT4
-
Note
Description
^C
1
The logic board is rebooted after changing this parameter.
mn
-
3
-
4.9.7.6 - DHW_COnF sub-menu
Point
Description
dhw_kp
DHW proportional gain
dhw_ki
DHW integral gain
dhw_dur
Duration of DHW production
dhw_stop Duration of DHW production stop
Note
Description
1
The logic board is rebooted after changing this parameter.
4.9.7.7 - DIS_COnF sub-menu
Point
Description
d_hl_off
Loop setpoint offset
d_hl_kp
Heating heat exchanger proportional
gain
d_hl_ki
Heating heat exchanger integral gain
d_dhw_kp DHW heat exchanger proportional gain -10.0 to 10.0 0.200
d_dhw_ki
DHW heat exchanger integral gain
-
4.9.7.8 - USeRCOnF sub-menu
-
Point
Description
-
language Language selection
-
use_pass User password
-
Note
Description
1
0 = English
1 = Spanish
2 = French
3 = German
4 = Italian
5 = Translation
Format
Default Units
1 to 300
300
1
1
1 to 300
120
1
1
No/Yes
Yes
20.0 to 80.0 65.0
20.0 to 80.0 58.8
20.0 to 80.0 52.5
20.0 to 80.0 46.3
20.0 to 80.0 40.0
20.0 to 80.0 33.3
20.0 to 80.0 26.7
20.0 to 80.0 26.7
Format
Default Units
-10.0 to 10.0 0.500
-10.0 to 10.0 0.050
-9.0 to 9.0
0.0
No/Yes
Yes
20.0 to 80.0 65.0
20.0 to 80.0 58.8
20.0 to 80.0 52.5
20.0 to 80.0 46.3
20.0 to 80.0 40.0
20.0 to 80.0 33.3
20.0 to 80.0 26.7
20.0 to 80.0 26.7
Format
Default Units
0 to 60
60
1
0 to 10
5
1
-10.0 to 10.0 0.200
-10.0 to 10.0 0.020
-10.0 to 10.0 0.200
-10.0 to 10.0 0.020
0 to 100
30
0 to 100
30
Format
Default Units
-10.0 to 10.0 0.500
-10.0 to 10.0 0.050
15 to 120
60
1
15 to 60
15
1
Format
Default Units
0.0 to 10.0
2.0
-10.0 to 10.0 0.200
-10.0 to 10.0 0.020
-10.0 to 10.0 0.020
Format
Default Units
0 to 5
0
1
1 to 9999
11
mn
mn
-
°C
°C
°C
°C
°C
°C
°C
°C
-
-
^C
-
°C
°C
°C
°C
°C
°C
°C
°C
mn
mn
-
-
-
-
%
%
-
-
min
min
^C
-
-
-
-
-
-