Device installation and connection
If, for technical reasons, a three-phase charging station is powered via a single-phase line, the terminals to be used are R, N and PE.
When the charging station is powered, the status LEDs will light up. After a quick status check, the light turns green and the display
shows the status message (according to the model). The station is ready and in standby either for user identification in order to
begin the recharge (Backend and RFID version), or for a recharge request (Autostart version). If the station encounters an operating
defect, the light on the corresponding socket-outlet (or both) will change colour according to the defect noted (refer to "Faults and
troubleshooting").
Line requisites
As the charging stations are equipped with Type B residual current protection (as shown in the electrical diagram attached), if a residual
current circuit breaker needs to be installed upstream of the power supply line, it must be of the same type.
7.55.4.502.0 - Installation and Operation Manual