Shorten Suspension Cable; Instrument Repair; Dismount; Dismounting Steps - WIKA LH-20 Manuel De Mise En Service

Masquer les pouces Voir aussi pour LH-20:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Fehlercode
Ursache
4 ... 20 mA
Level fluctuations
signal not
No atmospheric
stable
pressure compen-
sation
4 ... 20 mA
Connection to
signal
voltage supply
missing
wrong
No power supply
Operating voltage
too low or load
resistance too high
Current sig-
Electronics mo-
nal 3.6 mA;
dule or measuring
22 mA
cell defective
In Ex applications, the regulations for the
wiring of intrinsically safe circuits must
be observed.
6.3

Shorten suspension cable

Shorten the suspension cable individually.
Proceed as follows:
1. Remove the filter adapter from the capillary
line
2. Cut the suspension cable to the requested
length with side cutters
Caution:
Do not squeeze the capillary cable, as
this will impair the pressure compensati-
on. If necessary, rework the capillary with
a sharp knife.
3. Remove approx. 10 cm of the cable mantle,
strip off approx. 1 cm of insulation from the
ends of the wires
4. Insert the filter adapter
The work steps are finished.
6.4

Instrument repair

You can find information for a return shipment
under "Service" on our local website.
If a repair is necessary, please proceed as
follows:
Complete one form for each instrument
If necessary, state a contamination
WIKA Operating instructions - Submersible pressure transmitter model LH-20
Beseitigung
Adjust integration time via PACTware
Check the capillariy and cut it clean
Check the pressure compensation in the housing and clean the
filter element, if necessary
Check connection and correct, if necessary according to chapter
"Wiring plan"
Check cables for breaks; repair if necessary
Check, adapt if necessary
Exchange the instrument or send it in for repair
Clean the instrument and pack it damage-
proof
Attach the completed form and possibly also
a safety data sheet to the instrument
7
7.1
Take note of chapters "Mounting" and "Connec-
ting to power supply" and carry out the listed
steps in reverse order.
7.2
The instrument consists of materials which can
be recycled by specialised recycling companies.
We use recyclable materials and have designed
the parts to be easily separable.
Materials: see chapter "Technical data"
If you have no way to dispose of the old instru-
ment properly, please contact us concerning
return and disposal.

Dismount

Dismounting steps

Warning:
Before dismounting, be aware of
dangerous process conditions such as
e.g. pressure in the vessel or pipeline,
high temperatures, corrosive or toxic
products etc.

Disposal

21