12. Install the 15 Amp fuse into the fuse holder at top of the
control box.
13. Install the roof.
14. Restore utility power to the generator.
15. Push the ON/OFF Switch on the side of the generator to
the "ON" (I) position.
16. Set the generator mode to AUTO.
Replacing the Battery
1. Push the ON/OFF Switch on the side of the generator to
the "OFF" (0) position.
2. Remove utility power to the generator to de-energize the
battery charger.
3. Remove the roof.
4. Remove the 15 Amp fuse from the fuse holder at top of
the control box.
5. Remove the front panel.
6. Disconnect the negative (-) cable at the battery.
7. Disconnect the positive ( + ) cable at the battery.
8. Remove the battery and install replacement battery.
DON'T POLLUTE. CONSERVE RESOURCES.
RETURN USED BATTERY TO RECYCLING
COLLECTION CENTER.
9. Connect the positive ( + ) cable at the battery.
10. Connect the negative ( - ) cable at the battery.
11. Install the front panel.
12. Install the 15 Amp fuse into the fuse holder at top of the
control box.
13. Install the roof.
14. Restore utility power to the generator.
15. Push the ON/OFF Switch on the side of the generator to
the "ON" (I) position.
16. Set the generator mode to AUTO.
Charging the Battery
If it is necessary to charge the battery, proceed as follows:
1. Push the ON/OFF Switch on the side of the generator to
the "OFF" (0) position.
2. Remove utility power to the generator to de-energize the
battery charger.
3. Remove the roof.
4. Remove the 15 Amp fuse from the fuse holder at top of
the control box.
5. Remove the front panel.
6. Disconnect the negative (-) cable at the battery.
NOTICE Failure to disconnect negative battery cable
could result in equipment failure. DO NOT attempt to
jump start the generator. Damage to equipment resulting
from failure to follow this instruction will void engine and
generator warranty.
7. Charge battery with the battery charger at 2 Amps until
the battery holds 12 Volts. DO NOT exceed 13.7 volts
when charging the battery.
NOTICE DO NOT use a battery booster to quick charge a
low battery.
8. Connect the negative (-) cable at the battery.
9. Install the front panel.
10. Install the 15 Amp fuse into the fuse holder at top of the
control box.
11. Install the roof.
12. Restore utility power to the generator.
13. Push the ON/OFF Switch on the side of the generator to
the "ON" (I) position.
14. Set the generator mode to AUTO.
37