Electrical Field Connections - Briggs & Stratton GC1031 GENSET Mode D'emploi

Masquer les pouces Voir aussi pour GC1031 GENSET:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

1. Push the ON/OFF Switch (A) on the side of the generator
to the "OFF" (0) position. 
2. Remove utility power to the generator to de-energize the
battery charger. 
3. Remove the roof. 
4. Remove the 15 Amp fuse (B) from the fuse holder at top
of the control box.
5. Remove the front panel.
6. Disconnect the negative (-) cable at the battery.
7. Using a slotted screwdriver turn screws (C and D)
clockwise until they are snug (over tightening can
damage the mixer port).
8. Using a slotted screw driver turn screw (C)
counterclockwise ¼ turn.
9. Leave screw (D) seated.
10. Connect the negative (-) cable at the battery.
11. Install the front panel.
12. Install the 15 Amp fuse (B) into the fuse holder at top of
the control box. 
13. Install the roof. 
14. Push the ON/OFF Switch (A) on the side of the generator
to the "ON" (I) position. 
15. Open Control Panel access door and verify that the panel
is in Manual Mode.
16. Push and hold the CONFIG button to access the
configuration menu.
17. Push SELECT to edit the items in the configuration menu.
18. To setup the generators control board for LP fuel you will
need to enter the Configuration Menu by using the Dealer
Password, which is available on the Power Portal.
19. Navigate to "SELECT PROFILE" and press select on the
correct profile for the generator. For example "12KW_LP"
for operating a 12kW unit running on LP fuel.
NOTICE Selecting a profile that is not intended for the
generator can cause the generator to run erratically and
could result in damage.

Electrical Field Connections

WARNING
 Generator and utility voltage could cause electrical shock or burn resulting in death or serious injury.
• Installation must be performed by a licensed professional.
• Disconnect all sources of electricity before installing or servicing equipment.
• Ground system before applying power.
20
20. To Save the new fuel setting, press and hold the STOP/
CONFIG button until "Saving Settings..." is displayed.
21. For Additional information on the operation of the
generator controller please refer to the "Operation
Instructions GC1031 GENSET Controller Manual,"
PN: 80086364.