Sabiana DS-ST18 Série Instructions Pour L'installation, L'utilisation Et L'entretien page 24

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

English
- INSTALLATION
On the other hand, there are limitations in terms of the
minimum installation height of the radiant surfaces, ac-
cording to the average temperature values of the heating
fluid. The recommended minimum values are shown in
the table below, applicable for horizontal installations
and in relation to people who carry out stationary work.
MINIMUM RECOMMENDED ASSEMBLY HEIGHT
(in m compared to the floor) H
DS2-03 DS2-06
DS2-09
60°
3.00
3.10
70°
3.10
3.20
80°
3.20
3.30
90°
3.30
3.50
100°
3.40
3.70
110°
3.50
4.00
120°
3.60
4.20
130°
3.70
4.40
140°
3.80
4.60
- SUSPENSION METHODS
The Duck Strip radiant panels can be suspended in
various ways from the structures of the buildings. The
illustrations in this manual show several suspension
examples.
By fitting the tie rods in the relevant holes of the stiffening
crosspieces, on the upper part of the radiant panels, it
is possible to create non-visible suspensions arranged
with fixed and modular pitches of approximately 2 or
3 m. Since suspensions with a different pitch, ranging
between 1 and 2.5 m, are envisaged, the tie rods must
support the panel on the bottom side of the plate, or be
provided as indicated in the next pages.
Installation example:
24
O average
2
DS2-12 DS3-03 DS3-06
DS3-09
3.20
3.10
3.20
3.30
3.20
3.30
3.40
3.30
3.50
3.70
3.40
3.70
3.90
3.50
4.00
4.30
3.60
4.20
4.50
3.70
4.40
4.70
3.80
4.60
5.00
3.90
4.80
The suspension tie rods are not included in the supply of
the radiant panels and must be provided by the installer.
They can be installed with steel cables, with threaded
rods, with chains or with perforated straps and must be
adjustable.
The length of the suspension tie rods must be proportio-
nate to the total thermal expansion of the radiant strip: it
is therefore necessary to take into account both the total
maximum length and the average operating temperature
of the heat transfer fluid, in order to limit the angular
displacement of the tie rods to acceptable values.
The minimum length of the tie rods recommended for
DS3-12
the various lengths and for the various operating tem-
peratures of the Duck Strip radiant panels are indicated
3.30
3.40
in the relevant table.
3.60
Check that the chosen ceiling fastening system is
3.90
compatible with the weight of the panel and complies
4.20
4.40
with the standards in force.
4.70
4.90
The head and intermediate modules of the Duck Strip ra-
5.20
diant panels can be joined together by clamp-on sleeves,
in order to compose all the desired lengths.
The maximum distance between each suspension is 2 m.