- BENDING
Table of vertical bending f according the distance betwe-
en two suspension points.
BENDING f (mm)
Model
DS2-03
DS3-03
DS2-06
DS3-06
DS2-09
DS3-09
DS2-12
DS3-12
The table indicates the maximum bending expressed
in mm between two suspension points of the radiant
panels. The values refer to two distances between the
suspension points: 2 m and 3 m.
Models with a panel width between 900 and 1500 mm
cannot be suspended with distances between tie rods
exceeding 2 metres.
Avoid loading the radiant panels with a weight greater
than once the weight of the radiant panel.
The maximum curvature with respect to the longitudinal
axis on 6 m panels is 10 mm.
- CORRECT SPACING BETWEEN THE RA-
DIANT PANELS
It has been experimentally and practically found that the
good uniformity of heat irradiation over a central area of
a building (where the cooling effect of the outer walls
can be considered null) is obtained when the centre-to-
centre distance between two adjacent Duck Strip radiant
panels is equal to or less than the height from the floor.
For example, where the installation height of the radiant
panels is 4 m above the floor, the centre-to-centre distan-
ce of the adjacent Duck Strip panels must be set at 4 m
or less, in order to achieve the best heating uniformity.
Distance 2 m
3
1,5
3,5
2
3,5
2
3,7
2,5
NO
NOT
NEIN
NE PAS
NIET
40
mm