1 .3 . Indoor capacity range
1 .3 . 1 .
Connection Ratio
Connection Ratio = Total capacity index of the indoor units / Capac-
ity index of the outdoor units
Min. connection ratio
Type
Types of connected outdoor units
RELQ-T type
Single outdoor units
Double outdoor units
Types of connected indoor units
Type
When using only
FXDQ, FXMQ-P,
FXAQ
Single outdoor units
200% (*1)
Double outdoor units
*1. If the operational capacity of indoor units is more than 130%, low
airflow operation is enforced in all the indoor units.
1 .3 .2 . Outdoor Unit Combinations
Total capacity of indoor units needs to be within the specified range.
RELQ-T type
<Outdoor unit>
RELQ72TATJ*/TAYD*/TAYC*
RELQ96TATJ*/TAYD*/TAYC*
RELQ120TATJ*/TAYD*/TAYC*
RELQ144TATJ*/TAYD*/TAYC*
RELQ192TATJ*/TAYD*/TAYC*
RELQ240TATJ*/TAYD*/TAYC*
NOTE
Higher capacity than the above table can be selected, this may affect
heating and cooling capacity. For additional information see technical
engineering data.
3
70%
Max. connection ratio
When using only
FXTQ-PA, (CXTQ),
All other models
or at least one
FXFQ07/09
200% (*1)
130%
160% (*1)
<Total capacity index of indoor units>
. . . . . . . . . . . . .
51-93
. . . . . . . . . . . . .
68-124
. . . . . . . . . . . . .
84-156
. . . . . . . . . . . . . 101-187
. . . . . . . . . . . . . 135-249
. . . . . . . . . . . . . 168-312
1 .4 . Scope of the manual
This manual describes the procedures for handling, installing and
connecting the VRV Aurora series outdoor units. This manual has
been prepared to ensure adequate maintenance of the unit, and it will
provide help in case problems occur.
INFORMATION
The installation of the indoor unit(s) is described in the indoor unit
installation manual provided with the indoor unit(s).
2 . Accessories
2 . 1 . Accessories supplied with this unit
Confirm the following accessories are included. The storage location
of the accessories is shown in the figure below.
Accessories assy (piping)
NOTE
Do not throw away any of the accessories until installation is complete.
They are needed for installation work.
Name
Clamp (1)
Clamp (2)
Clamp (3)
Quantity
7 pcs.
1 pc.
1 pc.
Shape
(Small)
(Large)
Liquid side
Liquid side
Name
accessory
accessory
pipe (1)
pipe (2)
Quantity
1 pc.
1 pc.
Shape
72-120T
High and low gas
High and low gas
Name
side accessory
side accessory
pipe (1)
Quantity
1 pc.
Shape
72T
96-120T
Accessories assy (operation
and installation manual)
Vinyl tube
Manuals, etc.
5 pcs.
1 pc. each
• Operation Manual
• Installation Manual
• REQUEST FOR THE
INDICATION label
(Installation records)
Gas side
Gas side
accessory
accessory
pipe (1)
pipe (2)
1 pc.
1 pc.
72,96T 120T
72,96T 120T
L type
accessory joint
pipe (2)
1 pc.
2 pcs.
72-120T
3P477778-1J
English