Configuration Of Connection Pipe - Gree GWH09QB-K3DNA6C/I Manuel D'utilisation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Configuration of connection pipe

1. Standard length of connection pipe
● 5m, 7.5m, 8m.
2.Min. length of connection pipe is 3m.
3.Max. length of connection pipe and max. high difference.
Max length
Cooling
of connec-
capacity
tion pipe
5000Btu/h
(1465W)
7000Btu/h
(2051W)
9000Btu/h
(2637W)
12000Btu/h
(3516W)
18000Btu/h
(5274W)
4. The additional refrigerant oil and refrigerant charging required after prolonging
connection pipe
● After the length of connection pipe is prolonged for 10m at the basis of
standard length, you should add 5ml of refrigerant oil for each additional 5m
of connection pipe.
● The calculation method of additional refrigerant charging amount (on the basis
of liquid pipe):
Additional refrigerant charging amount = prolonged length of liquid pipe ×
additional refrigerant charging amount per meter
● Basing on the length of standard pipe, add refrigerant according to the
requirement as shown in the table. The additional refrigerant charging amount
per meter is different according to the diameter of liquid pipe. See the
following sheet.
Copyright 2018. This translation is property of GREE PRODUCTS SL. All rights reserved. Total or partial reproduction without its express authorization is prohibited.
Max height
difference
15
5
15
5
15
5
20
10
25
10
Max length
Cooling
of connec-
capacity
tion pipe
24000Btu/h
(7032W)
28000Btu/h
(8204W)
36000Btu/h
(10548W)
42000Btu/h
(12306W)
48000Btu/h
(14064W)
32
Max height
difference
25
10
30
10
30
20
30
20
30
20

Hide quick links:

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Gwh12qb-k3dna6c/iGwh18qd-k3dna6c/iGwh24qe-k3dna6g/i

Table des Matières