The above assignment of the functions to the control terminals is the
default setting of parameter Configuration 30 to value 110 or 410.
The functions can be assigned to the control terminals as required.
For more configurations, refer to the Operating Instructions.
Digital inputs (X210A.3 ... X210B.2): Low Signal: DC 0 V ... 3 V, High signal:
DC 12 V ... 30 V,
Input resistance: 2.3 kΩ, response time: 2 ms (STOA and STOB: 10 ms), PLC
compatible
Digital output S1OUT (X210B.3): Low Signal: DC 0 V... 3 V, High Signal:
DC 12 V ... 30 V,
Maximum output current: 50 mA, PLC compatible
Multifunction output MFO1 (X210B.4):
Digital output: Low Signal: DC 0 V... 3 V, High Signal: DC 12 V ... 30 V,
PLC compatible
Analog output: DC 19 ... 28 V, maximum output current: 50 mA, pulse-width
modulated (f
= 116 Hz),
PWM
Frequency signal: Output voltage: DC 0 V ... 24 V, maximum output current:
40 mA, maximum output frequency: 150 kHz
Multifunction input MF1 (X210B.6):
Analog signal: Input voltage: DC 0 ... 10 V (R
20 mA (R
=500 Ω),
i
Digital signal: Low Signal: DC 0 V ... 3 V, High signal: DC 12 V...30 V, response
time: 4 ms, PLC compatible
Conductor cross-section:
The signal terminals are suitable for the following cable sizes:
with ferrule:
0.25 ... 1.0 mm²
without ferrule: 0.14 ... 1.5 mm²
4.3.2 External 24 V power supply X210A.1 & X210A.2
NOTICE
Device damage possible
The digital inputs and the DC 24 V terminal of the electronic
control equipment can withstand external voltage up to DC 30 V.
Higher voltages may destroy the unit.
Avoid higher voltage levels.
Use suitable external power supply units with a maximum
output current of DC 30 V or use appropriate fuses to protect
the unit.
The bidirectional control terminals X210A.1/ X210A.2 can be used as a voltage
output or voltage input. By connecting an external power supply of DC
10/18
Technical data of control terminals
Quick Start Guide ACU
=70 kΩ), Input current: DC 0 ...