speed IN
direction
input 1
start
+26 V
remote
DC
input 2
GND
output 2
speed OUT
output 1
+5 V
speed intern
DC
Digitale Eingänge (TTL-Pegel)
Digital inputs (TTL-level)
Entrées numériques (niveau TTL)
Pin 2, remote
Pin 3, start
Pin 4, direction
Pin 6, input 1
Pin 8, input 2
Pin 13, speed intern
Analoge Eingänge
Analog inputs
Entrées analogiques
Pin 5, speed IN
0–5 V
/ 0–10 V
DC
DC
0–20 mA / 4–20 mA
Universal Ausgänge (PWM)
Universal outputs (PWM)
Sorties universelles (PWM)
Pin 14, output 1
Pin 15, output 2
Analog-Ausgang
Analog output
Sortie analogique
Pin 9, speed OUT
0-10 V
/ 0-7.2 kHz
DC
MCP PROCESS, 14-014, REV. C
Analogschnittstelle
Pin 9, speed OUT
Die werkseitige Einstellung ist
0 – 10V
, proportional zur
DC
Motordrehzahl 0 – 240.0 min–1.
Alternativ steht ein Frequenz-bereich
von 0 – 7.2 kHz zur Verfügung.
Wahlmöglichkeit mittels Schiebeschalter
S2 im Geräteinnern (siehe Seite 38).
Pin 10, +5 V
DC
Es stehen ca. +5 V
zur Verfügung.
DC
(max. Strom 0.5 A)
Pin 13, speed intern
Abhängig von der Betriebsart hat
Pin 13 unterschiedliche Funktionen:
Analogschnittstelle nicht aktiviert
(Normalbetrieb, d.h. Pin 2 offen) Hier
dient Pin 13 als Autostart-funktion. Ist
Pin 13 mit Pin 1 (GND) verbunden, kann
die Pumpe direkt über die Netzspannung
gestartet bzw. angehalten werden
(Netzschalter muss eingeschaltet sein).
Analogschnittstelle aktiviert
(Pin 2 auf GND)
– Pin 13 offen: Die Drehzahl wird über
Pin 5 (speed IN) vorgegeben.
– Pin 13 auf GND: Die Drehzahl kann
am Bedienungspanel der Pumpe
eingestellt werden.
Pin 14, output 1 (PWM)
Pin 15, output 2 (PWM)
Digitale Ausgänge in Verbindung mit Pin
7 (+26 V
), als Pulsweiten
DC
-Modulation ausgeführt (Open
Collector). Können nur über RS232-
Schnittstelle aktiviert werden; z.B. mit
einer Software wie ProgEdit.
Analog interface
Pin 9, speed OUT
The default setting is 0 – 10 V
DC,
proportionally to the motor
speed 0 – 240.0 rpm.
Alternatively a frequency range from
0 – 7.2 kHz is available. Alternatives with
sliding switch S2 inside the pump (see
Page 38).
Pin 10, +5 V
DC
About +5 V
are available.
DC
(max. current 0.5 A)
Pin 13, speed intern
Depending on how the pump is operated,
pin 13 has different functions: Analog
interface not activated (Normal operation,
i.e. pin 2 is open) Pin 13 serves as auto-
start function. If pin 13 is connected to
pin 1 (GND), the pump can be started
and stopped directly from the power
supply (the power switch must be on).
Analog interface activated
(Pin 2 on GND)
– Pin 13 open: The rotation speed is
adjusted via pin 5 (speed IN).
– Pin 13 on GND: The rotation speed
can be adjusted by the speed selector
on the control panel of the pump.
Pin 14, output 1 (PWM)
Pin 15, output 2 (PWM)
Digital outputs in connection with pin 7
(+26 V
), implemented as pulse-width-
DC
modulation (open collector). Can only
be activated via RS232 interface; e.g.
with a software like the ProgEdit.
Interface analogique
Pin 9, speed OUT
Le réglage d'usine par défaut est
0 – 10 V
, proportionnel au nombre de
CC
tours du moteur 0 – 240.0 t/min.
Une zone de fréquence de 0 – 7.2 kHz est
à disposition en alternative. Possibilité
de sélection au moyen d'un interrupteur
coulissant S2 à l'intérieur
de l'appareil (voir Page 38).
Pin 10, +5 V
CC
Environ +5 V
sont à disposition
CC
(courant maximal 0.5 A)
Pin 13, speed intern
Le pin 13 possède des fonctions
différentes en fonction du mode
d'opération: Interface analogue non
activée (Mode d'opération normal,
c.-à-d. pin 2 ouvert) Le pin 13 a la
fonction auto-start. Si le pin 13 est
connecté au pin 1 (GND), la pompe
peut être mise en route ou arrêtée
directement par l'alimentation électrique
(l'interrupteur principal doit être sur ON).
Interface analogique activée
(Pin 2 sur GND)
– Pin 13 ouvert: La vitesse de
rotation doit être ajustée par
le pin 5 (speed IN).
– Pin 13 sur GND: La vitesse de
rotation peut être ajustée par le
sélecteur de vitesse sur le tableau
de commande de la pompe.
Pin 14, output 1 (MLI)
Pin 15, output 2 (MLI)
Sorties numériques en relation avec le
pin 7 (+26 V
), mis en œuvre comme
CC
modulation de largeur d'impulsion
(collecteur ouvert). Ne peuvent être
activées que par l'interface RS232, p.e.
avec le logiciel ProgEdit.
37 of 63