DC Power Connection
DANGER! Be certain the switch is "OFF" prior to connecting the power cables to the power source or
installing the cable into the pump to prevent unexpected starting of the motor. Unexpected motor start can
cause unintended discharge of fuel, creating an explosion and fire hazard. Note that the switch does not
interupt power to the motor; it triggers a relay that tells the motor to turn on.
WARNING! BE CERTAIN the power cables are connected to the correct terminals at your power source.
REVERSING POLARITY WILL DAMAGE THE PUMP and void the warranty. Be certain to install provided
35 AMP fuse in the positive (red) wire. Failure to do so could damage the pump and void the warranty.
Inspect power cable before each use! Damage to the
outer jacket of the cable that exposes wiring requires
replacement of the power cable.
Install power cable by aligning flat on plug with back of
pump. Insert the plug into the motor housing as shown.
Lock into place using the threaded collar (A). Threaded
collar must be tightened completely to make proper
electrical connections. HAND TIGHTEN ONLY!
1. The green (ground) wire should be connected first.
Connect the green wire to the vehicle chassis or earth
ground. Install the DO NOT connect the green wire to
the negative power source post.
2. Next, connect the black (negative) wire to the negative
post of the DC power source.
3. Install the supplied fuse circuit protection on the
positive power wire or terminal prior to connecting it to
the power source.
4. Connect the red (positive) wire to the positive post last.
Disconnect in reverse order.

Tank Installation

The nextec 3200 series pump mounts to the bung of
a tank by way of the tank adapter that is bolted to the
inlet flange. The suction tube threads into the bottom
of the tank adapter, and must be cut to a length that
positions it at least 3" from the bottom of the tank. The
tank must be equipped with a vent cap.
Flat
Green
1
Earth /
Chassis
Ground
3" Min.
A
Black
Red
2
12 - 24 VDC
Typical Tank Installation