Installation Diagram - Presto 86710 Notice D'installation

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 1
A shock can also be interrupted from the keyboard of the automatic mechanism.
Access to the functions of the system is protected by access codes:
No code: Merely consulting results and events
Level 0: Manually launching shocks, rinsing, date/time/contrast adjustment and automatic change of the summer/winter
time + modifying level 0 password
Level 1: Level 0 + complete shock and rinsing configuration + level 1 password modification
Level 2: Level 1 + hardware configuration of the installation + level 2 password modification
PLC box overall dimensions 330 (H)* 400 (L)* 195 (D) mm
Protection index IP 65 (if all glands are shut-off).
Power supply 230 V~ 50 Hz - 16 A. The system is equipped with a differential circuit breaker 30 mA
Integrated transformer 230/12 VCA-75VA CE double insulation with thermal safety for:
-
2 3-way valves12 VAC 4VA
-
4 solenoid valves 12 VAC 5VA for controlling showers
-
1 solenoid valve 12 VAC 5VA for bleeding
-
2 way valves NF 230 VCA 10VA
Power supply 12 VAC/12 VDC for 8 presence detectors and 2 temperature probes.
Auxiliary contact NO or NC for hot water production control (max 5A -250 VAC)
Power supply of 2 circulation pumps 230 VAC 200 W Backlit display with numeric keypad.
1 red indicator lamp for indicating important events
Quick-disconnect terminal block for electrical connections
2 auxiliary configurable inputs (emergency stop, starting a shock.)
2 monitoring inputs of the position of 3-way valves
2 inputs for temperature sensors
2 inputs for presence detectors
Power supply 230V
Parameterable input:
Aux. 1
Aux. 2
Presence detector:
Zone 1
8 max to be split
over 2 zones
3-way solenoid valve A
3-way solenoid valve B
2 CHARACTERISTICS
Kit 1 looping Art. Nr. 86710
Art. Nr.
Description
86700
PLC box
86701
Temperature sensor A
90634
SV for manifold (DL discharge) or
draining
86626
3-way solenoid valve
85949
Presence detector (PIR)
85999
NC safety SV
90632
Manifold
90633
Capillary tube 25 metres

3 INSTALLATION DIAGRAM

86700
Zone 2
Safety solenoid
Kit 2 loopings Art. Nr. 86711
Qty
Art. Nr.
1
86700
1
86701
3
86702
90634
1
2
86626
1
85949
2
85999
2
90632
90633
Shower control
valve
solenoid valve
Description
PLC box
Temperature sensor A
Temperature sensor B
SV for manifold (DL discharge) or
draining
3-way solenoid valve
Presence detector (PIR)
NC safety SV
Manifold
Capillary tube 25 metres
Hot water production control
Temperature sensor A
T
Temperature sensor B
T
Circulation pump A
Circulation pump B
Draining solenoid valve
Qty
1
1
1
5
2
4
2
4
4

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

86711

Table des Matières