Checking the conditions:
Consideration
≥ 9 V
U
FG eff.
10.5 V ≥ 9 V
Final consideration:
From a purely functional point of view the bus segment shown in the example can be
operated based on the positive results.
Technical safety considerations
using variant Prosonic Flow 93***-***********G
Step 1 – compilation of technical values relevant to safety:
Fieldbus power supply (associated electrical apparatus)
FISCO Power Repeater KLD2-PR-Ex1.IEC1 (Pepperl+Fuchs):
• Nominal values:
U
=
15 V
o
I
=
207.2 mA
o
P
=
1.93 W
o
Described in the test certificate as "associated equipment". Suitable for connection to
a fieldbus system based on the FISCO model.
Prosonic Flow 93 (explosion protected electrical apparatus with intrinsically safe FF out-
put):
• Nominal values:
U
=
30 V
i
I
=
500 mA
i
P
=
5.5 W
i
10 µH
L
=
i
C
=
5 nF
i
Suitable for connection to a fieldbus system based on the FISCO model.
Cerabar S (explosion protected electrical apparatus with intrinsically safe FF output):
• Nominal values FISCO:
U
=
17.5 V
i
I
=
500 mA
i
P
=
5.5 W
i
10 µH
L
=
i
C
=
5 nF
i
Suitable for connection to a fieldbus system based on the FISCO model.
Bus cable type A (shielded bus cable):
• Nominal values:
24 Ω/km (loop resistance)
R'
=
C'
=
82 nF/km (capacitance per unit length)
623 µH/km (inductance per unit length)
L'
=
Condition met?
Yes
<
31