Endress+Hauser PROline prosonic flow 93 II2 GD Mode D'emploi page 66

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

<
28
Configuration example FISCO model
Fig. 11 shows the typical structure and the associated components. The field devices
are operated on a segment with the type of protection EEx ia. A galvanic isolator is used
for the transition to the area with explosion risk. Field devices with a lower power con-
sumption, such as the Cerabar S pressure gauge, are supplied via the two-wire line. In
contrast, the Prosonic Flow 93 as a four-wire device must be supplied via an local power
supply.
0 - 10 bar
0 - 10 bar
6
4
T
r
5
-
Esc
+
E
5
3
Fig. 11:
Typical example of a bus connection with a fieldbus power supply
Power Repeater KLD2-PR-Ex1.IEC1 (Pepperl+Fuchs)
1 = DCS with integrated FOUNDATION Fieldbus H1 interface card
2 = fieldbus power supply acc. FISCO model, Power Repeater KLD2-PR-Ex1.IEC1 (Pepperl+Fuchs)
3 = Prosonic Flow 93 bus devices for hazardous area
4 = terminator (T) = bus termination
5 = transducer supply
6 = Cerabar S bus devices for hazardous area
Functional considerations
Using the following procedure the functional considerations checks whether the desired
segment structure meets the basic requirements for transmission to the physical layer
in IEC 61158-2.
Step 1 – compilation of the functional characteristic values of the fieldbus components
• Fieldbus power supply according FISCO model, Power Repeater KLD2-PR-Ex1.IEC1
(Pepperl+Fuchs):
U
=
12.8 V (power supply voltage)
S
I
=
100 mA (power supply current)
S
• Fieldbus line:
Cable type A
44 Ω/km (effective resistance per unit length)
R
=
WK
• Fieldbus device Prosonic Flow 93:
I
=
12 mA (basic current)
B
U
=
9...32 V (perm. operating voltage)
B
I
=
0 mA (fault current)
FDE
I
=
0 (< I
)
startup
B
PROline Prosonic Flow 93 FOUNDATION Fieldbus
0 - 10 bar
0 - 10 bar
0 - 10 bar
6
r
r
Esc
Esc
5
-
Esc
+
-
+
E
E
3
3
E X
E X
6
580 m
T
r
5
Esc
-
+
E
2
3
Endress+Hauser
Fieldbus
Foundation
1

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Proline prosonic flow 93 ii1 gd

Table des Matières