Generator Sizing for SubDrive/MonoDrive
Basic generator sizing for the Franklin Electric SubDrive/MonoDrive system is 1 .5 times maximum input
watts consumed by the drive, rounded up to the next normal sized generator .
Recommended minimum generator sizes:
MonoDrive
1/2 hp = 2000 Watts (2 kW)
3/4 hp = 3000 Watts (3 kW)
1 hp = 3500 Watts (3 .5 kW)
MonoDriveXT
1 .5 hp = 4000 Watts (4 kW)
2 hp = 5000 Watts (5 kW)
SubDrive75 = 3500 Watts (3 .5 kW)
SubDrive100 = 5700 Watts (6 kW)
SubDrive150 = 7000 Watts (7 kW)
SubDrive300 = 11000 Watts (11 kW)
SubDrive2W = 6000 Watts (6 kW)
Note: Not to be used on GFIC circuit or externally regulated generators .
Verify voltage, hertz and idle speed are appropriate to supply drive .
Motor

Grounding/Generator Sizing

Service Entrance
Panel
Use the service
entrance panel
ground ONLY.
DO NOT run ground wire separate.
Motor ground wire MUST be bundled with motor wires.
Pump
Motor
7