TECHNICAL DATA

DESCRIPTION
Heating
Nominal heat input in heating mode
Nominal heat output (80°/60°)
Nominal heat output (50°/30°)
Reduced heat input (G20/G31)
Reduced heat output (80°/60°) (G20/G31)
Reduced heat output (50°/30°) (G20/G31)
Nominal Range Rated heat output (Qn)
Minimum Range Rated heat output (Qn) (G20/G31)
Useful efficiency Pn max - Pn min (80°/60°) (G20/G31)
Useful efficiency 30% (47° return) (G20/G31)
Combustion performance via analysis socket
Useful efficiency Pn max - Pn min (50°/30°) (G20/G31)
Useful efficiency 30% (30° return) (G20/G31)
Average Range Rated efficiency Pn (80°/60°)
Average Range Rated efficiency Pn (50°/30°)
Electric power
Pump electric power (1.000 l/h)
Category
Country of destination
Power supply voltage
Degree of Protection
Pressure drops at moment of stopping
Pressure drops on flue with burner on
Pressure drops on flue with burner at minimum
Maximum quantity of condensate (50/30°C - CH4)
Heating operation
Safety valve calibration pressure
Maximum operating pressure of heating circuit
Minimum pressure for standard operation
Maximum temperature
Selection field for H
O temperature in heating
2
Pump: maximum capacity available for the system
at an output of
Water content in the heating circuit
Gas pressure
Methane gas nominal pressure (G20)
LPG liquid gas nominal pressure (G31)
Hydraulic connections
Heating input - output
Gas input
Boiler dimensions
Height
Width
Depth of housing
Boiler weight
Flow rate
Air capacity
Flue gas capacity
Mass flow of flue gas (max-min)
(+) The installation of this product is allowed only in the destination Countries contained in the data plate, regardless of the present translation language.
14
MYNUTE GREEN 50 R.S.I.
kW
kcal/h
kW
kcal/h
kW
kcal/h
kW
kcal/h
kW
kcal/h
kW
kcal/h
kW
kcal/h
kW
kcal/h
%
97,4-97,6 / 96,8-97,5
%
%
%
106,2-108,0 / 103,2-105,9
%
%
%
W
W
V - Hz
IP
W
%
%
l/min
bar
bar
bar
°C
°C
mbar
l/h
l
mbar
mbar
Ø
Ø
mm
mm
mm
kg
G20
Nm
h
58,533
3/
Nm
/h
63,248
3
gr/s
21,210-3,851
47,00
40.420
45,78
39.369
49,91
42.926
9,00/12,00
7.740/10.320
8,78/11,70
7.554/10.062
9,72/12,71
8.359/10.929
47,00
40.420
9,00/12,00
7.740/10.320
102,5 / 100,1
97,0
108,0 / 106,2
97,6
106,9
162
92
II2H3P
(+)
230 - 50
X5D
69
3,00
1,30
5,2
3,5
4
0,25 ÷ 0,45
90
20/45 ÷ 40/80
500
1.000
3,2
20
37
1"
3/4"
764
553
284
39
G31
59,694
61,516
20,767-5,302