3.11.2 Connection of PureLink
Chlorine Generator Electronics to
a Zodiac AquaLink
The chlorine generator electronics in the PureLink
power center and the AquaLink RS controller require a
four (4) wire connection to communicate. Any outdoor
rated four (4) conductor cable, minimum 22 AWG
(0.326 mm
), can be used. Locate the appropriate screw
2
terminals on the circuit board according to Figures 15a
and 15b. Wire the chlorine generator power interface
board from the red 4-pin terminal bar to the AquaLink
RS red 4-pin terminal bar. See Figure 15a.
Wire the PureLink power center transformer to the load
side of the filter pump relay. See Figures 11 and 12.
Chlorine Generator
Power Interface Board
PureLink
Power Center
Figure 15a. Wiring a PureLink Control System
Network
|
Zodiac
Nature
Fusion Soft
Installation and Operation Manual
®
2®
TM
RS
®
Red, 4-Pin
Terminal Bar
4 3 2 1
All Button
OneTouch
or
3.12 Operation of External Control/ORP
Control Board
An external device such as an ORP (Oxidation
Reduction Potential) controller supplying 24 Volts AC
can be used to control the output of the chlorinator.
The chlorinator control board can be set up in the field
to operate in two (2) different modes. The mode of
operation is determined by the position of a movable
jumper J14. See Figure 16 for location.
Wait at least one (1) minute after applying
POS-1
power. See note 1.
With J14 jumper set to POS-1 and no voltage
applied to the ORP 24 VAC connector J15,
the chlorinator works normally displaying
the production rate of 0% to 100% on the
front of the power supply.
PDA
Transceiver
J-box for PDA
TM
Figure 15b. Wiring a PDA Control System Network
ENGLISH
Page 23
Red, 4-Pin
Terminal Bar
4 3 2 1
PureLink
Power Center