4.
STARTING
GB
4.1
Bridge the NC safety contacts with a jumper.
4.2
Before starting up, check the application type selected.
4.3
Any limit switches installed must be adjusted so that they are triggered near the mechanical opening and closing end stops.
Set TM=MAX.
Note: limit switches must be kept pressed until the operation has been completed.
4.4
If no limit switches are installed, bridge terminals 0-11 and 0-12 with jumpers and set TM to half.
4.5
Set TC=MAX. Set RF and R1 to half.
4.6
Using DIP2, set the direction.
4.7
Switch on power.
WARNING: The following operations are performed with no safety devices.
4.8
Perform opening and closing commands and check that the automation functions correctly and that the limit switches (if
installed) are correctly set.
Note: if mechanical stops are used to block the stroke of the automation, or a proximity limit switch with N.O. contact, adjust
the TM trimmer in order to obtain an operation time 2-3 s greater than the time effectively taken by the automation.
4.9
Connect the safety devices (removing the relative jumpers) and check that they function correctly.
4.10 If required, regulate the automatic closing by means of the TC trimmer.
4.11 Set RF to a position that allows the automation to function correctly while ensuring the safety of the user in the event of
collision.
4.12 Set obstacle thrust with R1.
Note: ensure that the forces exerted by the door wings are compliant with EN12453-EN12445 regulations.
4.13 Connect any other accessories and check operation.
4.14 Once the start up and check procedures are completed, close the container.
5.
TROUBLESHOOTING
Problem
Automation does not open
or close.
Automation opens but does
not close.
The automation is very
weak and does not invert
the movement.
External safety devices not
activating.
The remote control has li-
mited range and does not
work with the automation
moving.
E1 - IP1853
Possible causes
No power.
(POWER led off).
Short circuited accessories.
(POWER led off).
Blown line fuse.
(POWER led off).
Safety contacts are open.
(SA led on).
Release microswitch open.
(11 and 12 led on).
The motor thermal overload switch is open.
The remote control does not work.
The remote control does not work.
(SIG led flashing).
Safety contacts are open.
(SA led on).
Photocells activated.
(SA led on).
The automatic closing does not work.
The motor's condenser has an incorrect capacity
value.
Incorrect connections between the photocells and
the control panel.
The radio transmission is impeded by metal struc-
tures and reinforced concrete walls.
Check that the control panel is powered correctly.
Disconnect all accessories from terminals 0-1
(voltage must be 24 V=) and reconnect one at a
time.
Replace fuse.
Check that the safety contacts are closed correctly
(N.C.).
Check that the hatch is closed correctly and the
microswitch makes contact.
Check for continuity between the phases U-V-W of
the motor disconnected from the control panel.
Check the correct memorisation of the transmitters
on the incorporated radio.
Memory module BIXMR2 absent.
Check that the safety contacts are closed correctly
(N.C.).
Check that the photocells are clean and operating
correctly.
Check that the TC trimmer is not set at the maximum.
Replace the motor's condenser.
Connect NC safety devices together in series and
remove any bridges on the control panel terminal
board.
Install the antenna outside. Substitute the tran-
smitter batteries.
14
Remedy